Florida Form Energy PDF Details

In the sunny state of Florida, ensuring energy efficiency in buildings is not just a preference but a requirement, as governed by the comprehensive regulatory framework outlined in the Florida Building Code, Energy Conservation section. The Florida Energy Form, specifically Form 402, is central to this endeavor, applicable to a wide range of residential construction projects including new single- and multiple-family residences up to three stories high, additions and renovations to existing residential buildings, and the installation of new heating, cooling, and water heating systems. The form meticulously details the compliance process, requiring buildings to meet or exceed specified energy efficiency benchmarks presented in Table 402A along with mandatory requirements detailed in Table 402B. This adherence is crucial for the approval of new constructions, additions, or renovations, providing a structured path for builders and homeowners alike to contribute to Florida’s commitment to energy conservation. It addresses various construction features and sets strict limitations, such as the prohibition of electric resistance heating in attics and specific glass area restrictions, aimed at enhancing the energy performance of buildings. Additionally, the form includes provisions for exceptions under certain conditions and outlines the need for a certification statement, underscoring the importance of responsibility and accuracy in documenting energy compliance. Through this, the Florida Energy Form plays a pivotal role in steering construction practices towards sustainability and environmental stewardship, reflecting the state’s dedication to fostering energy-efficient living environments.

QuestionAnswer
Form NameFlorida Form Energy
Form Length2 pages
Fillable?No
Fillable fields0
Avg. time to fill out30 sec
Other namesflorida energy form, sample florida energy calculations worksheet, florida energy efficiency code form, florida energy forms

Form Preview Example

FORMS

Scope: Compliance with Section 402 of the Florida Building Code, Energy Conservation, shall be demonstrated by the use of Form 402 for single- and multiple-family residences of three stones or less in height, additions to existing residential buildings, renovations to existing residential buildings, new heatingbcoolingJ and water heating systems in existing buildings, as applicable.To comply, a building must meet or exceed all of the energy efficiency requirements on Table 402A and all applica le manoatory requirements summarized in Table 402B of this form. If a building does not comply with this method or Alternate Form 402, it may still comply under Section 405 of the Florida Building Code, Energy Conservation.

General Instructions:

constrLJcti.<m which incorporates any of the following features cannot comply using this method: glass areas in excess of 20 pen:::ent of conditioned floor area, electric resistance located in attics. Additions:::; 600 sq .ft., renovations and equipment change outs may comply by this method with exceptions given.

applicable spaces of the "To Be Installed" column on Table 402A with the information requested. All "To Be Installed" values must be equal to or more efficient than the

"To Be Installed" column information.

402B and check each box to indicate your intent to comply with all applicable items.

"Prepared By" certification statement at the bottom of page 1. The owner or owner's agent must also sign and date the form.

1.New construction, addition, or existing building

2.Single-family detached or multiple-family attached

3.If multiple-family-No. of units covered by this submission

4.Is this a worst case? (yes/no)

5.Conditioned floor area (sq. ft.)

6.Glass type and area:

Please Print

CK

1.

2.

3.

4.

5.

U-factor

b.SHGC

7.Percentage of glass to floor area

8.Floor type, area or perimeter, and insulation:

6a.

6b.

6c.

sq. ft.

7.

%

Slab-on-grade (R-value) b. Wood, raised (R-value)

Wood, common (R-value)

d.Concrete, raised (R-value)

common (R-value)

9.Wall type, area and insulation:

l. Masonry (Insulation R-value) Wood frame (Insulation R-value)

b. Adjacent: 1. Masonry (Insulation R-value) Wood frame (Insulation R-value)

10. Ceiling type, area and insulation:

Under attic (Insulation R-value)

Single assembly (Insulation R-value)

11.Air distribution system: Duct insulation, location, Qn

Duct location, insulation b. AHU location

Qn, Test report attached(< 0.03; yes/no)

12. Cooling system:

Type

b.Efficiency

13.Heating system:

Type

b. Efficiency

Sa. R:::

lin. ft.

8b. R:::

sq. ft.

ac. R=

sq. ft.

8d. R:::::

sq. ft.

ae. A=

sq. ft.

9a-i. A=

sq. ft.

9a-2.

R=

sq. ft.

9b-1.

R::::

sq. ft.

9b-2.

R::::

sq. ft.

10a. R=

sq. ft.

 

10b. R-

 

sq. ft.

11a. R:::: ____

 

 

11b. ----------------

 

11 c.Test report attached? Yes

No

14.

HVAC sizing calculation: attached

14. Yes No

 

 

15.

Hot water system:

 

 

 

15a.

 

 

15b.

plans and specifications covered by the calculation are in compliance with the Florida Review of plans and specifications covered by this calculation indicates compliance with the Florida Energy Code. Before construction is completed, this building will be inspected for compliance in accordance with Section 553.908, F.S.

DATE: ____

CODE OFFICIAL:___________________.

rnrtiht エィセエエィゥッ@building is in compliance with the Florida Energy Code:

DATE: ____

C.4

2010 FLORIDA BUILDING CODE- ENERGY CONSERVATION

FORMS

TABLE402A

BUILDING COMPONENT

Windows (see Note 2):

Skvliahts

セイウZ@Exterior door U-Factor Floors: Slab-on-grade

Over unconditioned spaces (see Note 3) Walls- Ext. and Adj. (see Note 3):

Frame

Mass (see Note 3) Interior of wall: Exterior of wall:

Ceilings (see Notes 3 & 4)

Reflectance

Air distribution system (see Note 4)

Ductwork & air handling unit:

Unconditioned space

Conditioned space

Duct A-value

Air leakage On

Air conditionina svstems (see Note 5) Heating system

Heat pump (see Note 5)Cooling: Heating:

Gas furnace Oil furnace

Electric resistance: Not allowed (see Note 5)

Water heating system (storage type)

Electric (see Note

Gas fired (see Note 7):

Other (describe):

PERFORMANCE CRITERIA'

U-Factor < 0.65 SHGC=0.30 %of CFA <::: 20% U-Factor < 0.75 U-Factor < 0.65 No requirement R-13

R-13

R-7.8

R-6

R=30

0.25

Not allowed

A-value<: 6

On セPNPS@

SEER= 13.0

SEER 13.0

HSPF = 7.7

AFUE78%

AFUE78%

40 gal: EF = 0.92

50 gal: EF = 0.90

40 gal: EF = 0.59

50 gal: EF 0.58

INSTALLED VALUES:

U-Factor=

SHGC=

%of CFA=

U-Factor=

R-Value =

A-Value

A-Value=

A-Value-

A-Value=

Test report

Attached?

Reflectance =

Yes/No

 

Location:

Test report

 

 

Attached?

 

Yes/No

R-Value

 

On=

 

SEER=

 

SEER=

 

HSPF=

 

AFUE=

 

AFUE=

 

Gallons

 

EF=

 

Gallons=

 

EF=

 

(1)Each component present in the As Proposed home must meet or exceed each of the applicable performance criteria in order to comply with this code using this method; otherwise Section 405 compliance must be used.

(2)Windows and doors qualifying as glazed fenestration areas must comply with both the maximum U-Factor and the maximum SHGC (solar Heat Gain Coefficient) criteria and have a maximum total window area equal to or less than 20% of the conditioned floor area (CFA); otherwise Section 405 must be used for compliance. Exception: Additions of 600 square feet (56 m2) or less may have a maximum glass to CFA of 50 percent.

(3)A-values are for insulation material only as applied in accordance with manufacturers' installation instructions. For mass walls, the "interior of wall" requirement must be met except if at least 50% of the R-6 insulation required for the "exterior of wall" is installed exterior of, or integral to, the wall.

(4)Ducts & AHU installed substantially leak free per Section 403.2.2.1. Test by Class 1 BERS rater required.

Exception: Ducts installed onto an existing air distribution system as part of an addition or renovation; duct must be R-6 installed per Sec. 503.2.7.2.

(5) For all conventional units with capacities greater than 30,000 Btu/hr. For other types of equipment, see Tables 503.2.3(1-8).

Exception: The prohibition on electric resistance heat does not apply to additions, renovations and new heating systems installed in existing buildings.

(6)For other electric storage volumes, minimum EF = 0.97-(0.00132 x volume).

(7)For other natural gas storage volumes, minimum EF =0.67-(0.0019 x volume).

TABLE 4028 MANDATORY REQUIREMENTS

 

 

COMPONENTS

SECTION

REQUIREMENTS

I

CHECK

 

 

To be caulked, gasketed, キ・。エィ・イウエイゥーセ・、@or otherwise sealed. Recessed lighting !C-rated as meeting ASTM E

 

 

Air leakage

402.4

283. Windows and doors= 0.30 cfm/sq.ft. Testing or visual inspection required. Fireplaces: gasketed doors &

 

 

 

 

outdoor combustion air.

 

 

Ceilings/knee walls

405.2.1

R-19 space permitting.

 

 

Programmable thermostat

403.1.1

Where forced-air furnace is primary system, programmable thermostat is required.

 

 

Air distribution system

403.2

Ducts in attics or on roofs insulated to R-8; other ducts R-6. Ducts tested to a. = 0.03 by a Class 1 BERS rater.

 

 

 

 

Heat trap required for vertical pipe risers. Comply with efficiencies in Table 403.4.3.2. Provide switch or clearly

 

 

Water heaters

403.4

marked circuit breaker (electric) or shutoff (gas). Circulating system pipes insulated to= R-2 +accessible manual

 

 

 

 

OFF switch.

 

 

 

 

Spas and heated pools must have vapor-retardant covers or a liquid cover or other means proven to reduce heat

 

 

Swimming pool &spas

403.9

loss except if 70% of heat from site-recovered energy. Off/timer switch required. Gas heaters minimum thermal

 

 

 

 

efficiency- 78% (82% after 4/16/13). Heat pump pool heaters minimum COP- 4.0.

 

 

 

 

Sizing calculation performed &attached. Minimum efficiencies per Tables 503.2.3. Equipment efficiency verification

 

 

Cooling/heating equipment

403.6

required. Special occasion cooling or heating capacity requires separate system or variable capacity system.

 

 

 

 

Electric heat >10kW must be divided into two or more stages.

 

 

Lighting equipment

404.1

At least 50% of permanently installed lighting fixtures shall be high-efficacy lamps.

 

 

2010 FLORIDA BUILDING CODE- ENERGY CONSERVATION

C.5

How to Edit Florida Form Energy Online for Free

When using the online PDF editor by FormsPal, you're able to fill out or modify florida form energy here and now. The editor is consistently maintained by us, getting awesome functions and becoming a lot more versatile. All it requires is a couple of basic steps:

Step 1: Firstly, open the tool by pressing the "Get Form Button" at the top of this site.

Step 2: As you start the PDF editor, there'll be the document ready to be filled out. Besides filling in different fields, you may as well perform various other actions with the Document, that is putting on any words, changing the original text, adding graphics, signing the PDF, and much more.

This PDF requires specific data to be entered, so make sure you take your time to provide what's required:

1. To begin with, when filling in the florida form energy, begin with the form section that features the following fields:

Completing part 1 in energy compliance form florida

2. Your next part is usually to fill out the next few blanks: Percentage of glass to floor area, Floor type area or perimeter and, Slabongrade Rvalue b Wood raised, Wood common Rvalue d Concrete, common Rvalue, Wall type area and insulation, l Masonry Insulation Rvalue, Wood frame Insulation Rvalue, b Adjacent, Masonry Insulation Rvalue, Wood frame Insulation Rvalue, Ceiling type area and insulation, Under attic Insulation Rvalue, Air distribution system Duct, and Duct location insulation.

Completing section 2 in energy compliance form florida

3. This 3rd segment is considered rather simple, plans and specifications covered, rnrtiht building is in compliance, DATE, DATE, Review of plans and specifications, CODE OFFICIAL, and FLORIDA BUILDING CODE ENERGY - all of these empty fields is required to be filled out here.

energy compliance form florida writing process clarified (part 3)

4. The subsequent paragraph requires your attention in the following parts: Test report Attached YesNo, Test report Attached YesNo, BUILDING COMPONENT, PERFORMANCE CRITERIA, INSTALLED VALUES, Windows see Note, Skvliahts, ZExterior door UFactor, Floors Slabongrade, Over unconditioned spaces see Note, Walls Ext and Adj see Note Frame, see Note, Interior of wall Exterior of wall, Ceilings see Notes Reflectance, and Air distribution system see Note. Be sure you provide all of the needed info to go forward.

Part no. 4 of submitting energy compliance form florida

As for Ceilings see Notes Reflectance and Walls Ext and Adj see Note Frame, make sure you take a second look in this section. These two are certainly the key fields in this file.

5. Last of all, this final section is what you'll want to finish prior to closing the PDF. The blanks in this case are the next: COMPONENTS, SECTION, REQUIREMENTS, CHECK, Air leakage, Ceilingsknee walls, Programmable thermostat, Air distribution system, Water heaters, Swimming pool spas, Coolingheating equipment, To be caulked gasketed or, R space permitting, Where forcedair furnace is primary, and Spas and heated pools must have.

Part number 5 of filling in energy compliance form florida

Step 3: Always make sure that the details are correct and then simply click "Done" to complete the project. Acquire your florida form energy the instant you sign up at FormsPal for a 7-day free trial. Conveniently gain access to the document inside your personal account, with any edits and changes all kept! When you use FormsPal, you can fill out forms without stressing about personal information leaks or data entries getting distributed. Our protected platform helps to ensure that your private details are maintained safe.