Content Form PDF Details

A content form is a document that has been established for the purpose of creating a contract between two or more parties. The content of the form typically includes information about what will happen in case one party fails to uphold their end of the agreement, and needs to be signed by all parties before any money changes hands. For example, if you are buying a house from someone else, they might request a signature from you agreeing that should anything go wrong with your mortgage payments then they can take back the property without any notice. This would be called an "equity release." A content form can also be used when there is no formal written agreement in place but both sides agree on something verbally or over email.

If you need to first determine how much time you need to complete the content form and how many pages it's got, here is some basic information that may be useful.

QuestionAnswer
Form NameContent Form
Form Length4 pages
Fillable?Yes
Fillable fields123
Avg. time to fill out25 min 40 sec
Other namesfire alarm inspection form excel, fire form inspection alarm, fire alarm testing inspection, fire inspection alarm form

Form Preview Example

INSPECTION, TESTING, AND MAINTENANCE

72-101

 

INSPECTION ANDTESTING FORM

 

DATE:

 

TIME:

SERVICE ORGANIZATION

PROPERTY NAME (USER)

Name:

Name:

Address:

Address:

Representative:

Owner Contact:

License No.:

Telephone:

Telephone:

 

MONITORING ENTITY

APPROVING AGENCY

Contact:

Contact:

Telephone:

Telephone:

Monitoring Account. Ref. No.:

 

TYPE TRANSMISSION

SERVICE

□ McCulloh

□ Weekly

□ Multiplex

□ Monthly

□ Digital

□ Quarterly

□ Reverse Priority

□ Semiannually

□ RF

□ Annually

□ Other (Specify)

□ Other (Specify)

Control Unit Manufacturer:

Model No.:

Circuit Styles:

 

Number of Circuits:

 

Software Rev.:

 

Last Date System Had Any Service Performed:

Last Date that Any Software or Configuration Was Revised:

ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity

Circuit Style

Manual Fire Alarm Boxes

Ion Detectors

Photo Detectors

Duct Detectors

Heat Detectors

Waterflow Switches

Supervisory Switches

Other (Specify):

Alarm verification feature is disabled

enabled

(NFPA Inspection and Testing, 1 of 4)

FIGURE 10.6.2.3 Example of an Inspection and Testing Form.

2002 Edition

72-102

NATIONAL FIRE ALARM CODE

ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION

Quantity

Circuit Style

Bells

Horns

Chimes

Strobes

Speakers

Other (Specify):

No. of alarm notification appliance circuits:

Are circuits monitored for integrity?

J Yes

No

SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity

Circuit Style

Building Temp.

Site Water Temp.

Site Water Level

Fire Pump Power

Fire Pump Running

Fire Pump Auto Position

Fire Pump or Pump Controller Trouble

Fire Pump Running

Generator In Auto Position

Generator or Controller Trouble

Switch Transfer

Generator Engine Running

Other:

SIGNALING LINE CIRCUITS

Quantity and style of signaling line circuits connected to system (see NFPA 72, Table 6.6.1):

QuantityStyle(s)

SYSTEM POWER SUPPLIES

 

 

(a) Primary (Main): Nominal Voltage

Amps

 

Overcurrent Protection: Type

Amps

 

Location (of Primary Supply Panelboard):

 

 

Disconnecting Means Location:

 

 

(b) Secondary (Standby):

 

 

Storage Battery: Amp-Hr. Rating

 

Calculated capacity to operate system, in hours:

24

60

Engine-driven generator dedicated to fire alarm system:

Location of fuel storage:

TYPE BATTERY

Dry Cell

Nickel-Cadmium

Sealed Lead-Acid

Lead-Acid

Other (Specify):

(c)Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply: Emergency system described in NFPA 70, Article 700

Legally required standby described in NFPA 70, Article 701

Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements ofArticle 700 or 701.

(NFPA Inspection and Testing, 2 of 4)

FIGURE 10.6.2.3 Continued

2002 Edition

INSPECTION, TESTING, AND MAINTENANCE

72-103

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE

Yes

No

Who

Time

Monitoring Entity

 

 

Building Occupants

J

 

 

Building Management

 

 

Other (Specify)

 

 

AHJ Notified ofAny Impairments

J

 

 

SYSTEM TESTS AND INSPECTIONS

TYPE

Visual

Functional

Comments

Control Unit

 

Interface Equipment

J

 

Lamps/LEDS

 

Fuses

 

Primary Power Supply

 

Trouble Signals

 

Disconnect Switches

J

 

Ground-Fault Monitoring

 

SECONDARY POWER

 

 

 

TYPE

Visual

Functional

Comments

Battery Condition

 

 

Load Voltage

 

 

Discharge Test

 

 

Charger Test

 

 

Specific Gravity

 

 

TRANSIENT SUPPRESSORS

 

 

REMOTE ANNUNCIATORS

 

NOTIFICATION APPLIANCES

 

 

 

Audible

J

 

Visible

 

Speakers

 

Voice Clarity

 

 

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS

Loc. & S/N

Device

Visual

Functional

Factory

Measured

Pass

Fail

Type

Check

Test

Setting

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J

 

 

 

 

 

 

Comments:

(NFPA Inspection and Testing, 3 of 4)

FIGURE 10.6.2.3 Continued

2002 Edition

72-104

NATIONAL FIRE ALARM CODE

 

 

EMERGENCY COMMUNICATIONS EQUIPMENT

 

Visual

Functional

Comments

Phone Set

 

 

 

Phone Jacks

 

 

J

 

Off-Hook Indicator

 

 

 

Amplifier(s)

 

 

 

Tone Generator(s)

 

 

J

 

Call-in Signal

 

 

 

System Performance

 

 

 

 

 

Visual

Device

Simulated

INTERFACE EQUIPMENT

 

Operation

Operation

 

 

 

 

 

(Specify)

 

 

J

(Specify)

 

 

(Specify)

 

 

SPECIAL HAZARD SYSTEMS

 

 

 

 

 

(Specify)

 

 

(Specify)

 

 

J

(Specify)

 

 

Special Procedures:

 

 

 

 

 

Comments:

 

 

 

 

 

SUPERVISING STATION MONITORING

Yes

No

Time

Comments

Alarm Signal

J

 

 

 

Alarm Restoration

J

 

 

 

Trouble Signal

J

 

 

 

Supervisory Signal

J

 

 

 

Supervisory Restoration

J

 

 

 

NOTIFICATIONS THAT TESTING IS COMPLETE

Yes

No

Who

Time

Building Management

J

 

 

 

Monitoring Agency

J

 

 

 

Building Occupants

J

 

 

 

Other (Specify)

J

 

 

 

The following did not operate correctly:

 

 

 

 

 

System restored to normal operation: Date:

 

Time:

 

 

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

 

Name of Inspector:

 

 

Date:

 

Time:

Signature:

 

 

 

 

 

Name of Owner or Representative:

 

 

 

 

 

Date:Time:

Signature:

(NFPA Inspection and Testing, 4 of 4)

FIGURE 10.6.2.3 Continued

2002 Edition

How to Edit Content Form Online for Free

The PDF editor helps make writing documents stress-free. It is really convenient to modify the Content Form document. Adhere to all of these actions if you would like do it:

Step 1: At first, pick the orange "Get form now" button.

Step 2: As soon as you enter our fillable fire inspection form editing page, you'll see all of the actions you may take with regards to your template within the upper menu.

The next parts are contained in the PDF form you'll be filling in.

step 1 to writing fire alarm inspection form

In the SERVICE □ Weekly □ Monthly □, Model No, TYPE TRANSMISSION □ Mc, Cull, oh □, Control Unit Manufacturer: Circuit, Quantity, ALARM, INITIATING DEVICES AND, Manual Fire Alarm Boxes Ion, Alarm verification feature is, enabled, and (NFPA Inspection and Testing field, put down the information you have.

fire alarm inspection form SERVICE □ Weekly □ Monthly □, Model No, TYPE TRANSMISSION □ McCulloh □, Control Unit Manufacturer: Circuit, Quantity, ALARM-INITIATING DEVICES AND, Manual Fire Alarm Boxes Ion, Alarm verification feature is, enabled, and (NFPA Inspection and Testing blanks to complete

You may be expected to write down the details to let the program complete the segment NOTIFICATIONS ARE MADE Monitoring, PRIOR TO ANY TESTING No □ □ □ □ □, Yes □ J □ □ J, Who, Time, TYPE Control Unit Interface, SYSTEM TESTS AND INSPECTIONS, Visual, Functional, Comments, □ J □ □ □ □ J □, Visual, Functional, and Comments.

step 3 to finishing fire alarm inspection form

You should include the rights and responsibilities of the sides inside the TYPE Control Unit Interface, J □ □, INITIATING AND SUPERVISORY DEVICE, Loc, Device Type, Visual Check, □ □ □ □ J □, Factory Setting, Measured Setting, Functional, Test □ □ □ □ □ □, Pass □ □ □ □ □ □, Fail □ □ □ □ □ □, Comments:, and FIGURE 10 space.

TYPE Control Unit Interface, J □ □, INITIATING AND SUPERVISORY DEVICE, Loc, Device Type, Visual Check, □ □ □ □ J □, Factory Setting, Measured Setting, Functional, Test □ □ □ □ □ □, Pass □ □ □ □ □ □, Fail □ □ □ □ □ □, Comments:, and FIGURE 10 in fire alarm inspection form

Finalize by reading the next fields and preparing them accordingly: EMERGENCY COMMUNICATIONS EQUIPMENT, Visual, Functional, □ J □ □ J □ □, Comments, INTERFACE EQUIPMENT, (Specify) (Specify) (Specify), SPECIAL HAZARD SYSTEMS, (Specify) (Specify) (Specify), Special Procedures:, Comments:, SUPERVISING STATION MONITORING, Yes J J J J J Yes J J J J, Visual, and Device.

Completing fire alarm inspection form part 5