Inkbird Itc 100 Manual Form PDF Details

In the realm of temperature control, precision is paramount, and the Inkbird ITC-100 Manual form emerges as a comprehensive guide to mastering such precision. The manual astutely covers a range of imperative topics, including safety warnings that underscore the need for adherence to specifications for avoiding hazards like electric shock or fire. It delves into the product features, showcasing its compatibility with a variety of temperature sensors and its ability to operate across a wide temperature spectrum with remarkable accuracy. With a detailed exposition on technical parameters and models, the manual serves the double purpose of a straightforward guide for installation and a technical handbook for troubleshooting. It thoroughly explains the installation process through diagrams and wiring instructions, ensuring users can easily set up their temperature controllers. Furthermore, the operational instructions provide a clear roadmap to navigating the controller’s functionalities from basic setup to advanced features like self-tuning for optimal PID control parameters. This mixture of safety protocols, installation guidelines, precise control features, and troubleshooting advice encapsulates the essence of the Inkbird ITC-100 Manual, making it an indispensable resource for anyone looking to harness the sophisticated temperature control capabilities of the ITC-100 PID Temperature Controller.

QuestionAnswer
Form NameInkbird Itc 100 Manual Form
Form Length9 pages
Fillable?No
Fillable fields0
Avg. time to fill out2 min 15 sec
Other namesinkbird itc 100 manuale italiano, inkbird itc 100 manual italiano, inkbird itc 100rh manuale italiano, itc 100vh manual

Form Preview Example

ITC-100 PID Temperature Controller

User Manual

V1.0 2015-6-30

Contents

Safety warning …………………………………………………………………………………………………………………………………2

Product features .………………………………………………………………………………………………………………………………2

1.Technical parameters …………………………………………….…………………………………………………………………………2

2.Models and specifications ..…………………………………………………………………………………………………………………2

3.Diagram and installing size …………………………………………………………………………………………………………………2

4.Wiring diagram ………………………………………………………………………………………………………………………………2

4.1Connecting sensors …….….……………………………………………………………………………………………………………3

4.1.1Thermocouple ………………………...………………………………………………………………………………………………3

4.1.2Dual lines PT100 sensor……….……..………………………………………………………………………………………………3

4.1.3RTD sensor……….……………………………...……………………………………………………………………………………3

4.2Power supply connection ……………..…………………………………………………………………………………………………3

4.3connection for control signal output ……………………………………………………………………………………………………3

4.4Connection for alarm control ……………………………………………………………………………………………………………3

5.Panel instruction ……………..………………………………………………………………………………………………………………3

6.Operation instruction ...………………………………………………………………………………………………………………………3

6.1Display status ……………..………………………………………………………………………………………………………………3

6.2View output value ………………………………...………………………………………………………………………………………3

6.3Automatic/Manual control switch ………………………………………………………………………………………………………3

6.4Value setting ……………...………………………………………………………………………………………………………………3

6.5Launch self-tuning function ……...………………………………………………………………………………………………………3

6.6Workflow for setting …………………………………………………………………………………………………………………...…4

6.7Parameters setting ………………………………………………………………………………………………………………………4

6.8Parameters related to alarm output: “HiAL,LoAL,dHAL,dHAL,dF,ALP,CF” ……..……………….……………..……………………5

6.8.1Alarm parameters: HiAL,LoAL,dHAL,dHAL …………………………….……………………………………………………….…5

6.8.2Defining parameter for alarm ALP ………………………………………………………………………..………………………5

6.8.3Hysteresis Band dF …………………………………………………………………………………………………………………5

6.8.4Function parameter CF ……………………………………………………………………………………………………………..5

6.9Parameters related to input “Sn,diP,diL,diH,DL,Sc” …………………………………………………………………….……………5

6.9.1Sensor type input “Sn” …………………………………………………………………………………………………………...…5

6.9.2Decimal point position“diP” …………………………………………………………………………………………………………5

6.9.3Definition parameters "diH" and "diL" for linear input range …………………………..…………………………………………5

6.9.4Filtering parameter“dL”………………………………………………………………………………………………………………5

6.9.5Sensor Calibration“Sc”………………………………………………………………………………………………………………5

6.10Parameters related to control output“oPI,oPL,oPH,CtrL” …………………………………………………………………...………5

6.10.1Output mode parameters "oPI", "oPL" and "oPH" are used for limiting output …………………………………………..……5

6.10.2Adjustment mode parameter "CtrL" ………………………………………………………………………………………………6

6.11PID control parameters related to self-tuning “M50, P, t” and functional parameter “CtL”……………………………………..6

6.11.16.11.1 Holding parameter "M50" …………………………………………………………………………………………………..6

6.11.2Rate parameter "P" ……………………………………………………………………………………….………………………6

6.11.3Hysteresis time "t"…………………………………………………………………………………………………………..………6

6.11.4Function parameter "CtL" ………………………………………………………………………………………………………….6

6.12Communication parameter “AddrbAud” ……………………………………………………………………………………………6

6.13Field parameter "EP1 - EP8" ……………………..……………………………………………………………………………………7

6.14Permission for parameters “Loc”“LOC” ……………………………………………………………………………………………7

6.15Common faults and handling methods ……………………………………………………………………………….………………7

7 Wiring instruction ……………………………………………………………………………………………………………………………7

7.1Directly control load by the internal relay of the instrument ..…………………………………………………………………………7

7.2Control the load via external contactor …………………………………………………………………………………………...……7

7.3SSR control ……………………………….……………………………………………………………………………………………7

7.4Solenoid valve or relay control ………..………………………………………………………………………………………………8

7.5Control load via external contactor (24V) …………………………………………………………………………………………..…8

8.Field application example …………………………………………………………………………………………………………………..8

 

© 2015 Inkbird Inc. All rights reserved.

1

www.ink-bird.com, CS@ink-bird.com

Safety warning

It’s a must to use this product within its specification and using scope.

When power on, do not connect, disassemble and touch terminals, as those may cause damage due to spark, malfunction or electric shock.

No metal fragment, wire thread or metal dusts produced during installation are allowed to be inside the device, otherwise, there will be risk of electric shock, fire or malfunction.

Please do not use this product in flammable and explosive locations, otherwise, there will be risk of damage caused by explosion.

Never disassemble, refit and repair this product, or touch the inner components by yourself, otherwise, there will be risk of electric shock, spark or malfunction.

If the replay was serving beyond its estimated lifetime, there will be risk of

contact fusion and burning. It’s a must to always pay attention to the using

environment of relay, and using the relay within its rated load and estimated lifetime. The estimated lifetime of the relay varies according to the output load and switching condition.

Product features

Panel size: DIN(48×48mm)

Compatible with various temperature sensors (K, S, Wre, T, E, J, B, N, CU50, PT100)

Wide control temperature range: -50 - 1300ºC ( type K thermocouple)

Display and control accuracy: 0.1 ºC, high measuring precision: ±0.2%FS

PID control mode with high-performance self-tuning function User-defined output and alarm modes

Adjustable digital filtering for reducing external interference

Self-calibration available for ensuring long term stability of the instrument high luminance LED screen with height 0.39“ characters,

anti-dazzle panel, well visibility

Inbuilt switching power supply applicable for wide voltage range with low power consumption

1.Technical parameters

 

AC 100-240V 50/60Hz

 

 

Rated Voltage

AC/DC 12-24V 50/60Hz

 

 

 

DC 12-24V

 

 

Working voltage

85 to 100% of the rated voltage

 

 

 

About 5VA (100V - 240VAC)

 

 

Power

About 4VA (12V - 24VAC)

 

 

 

About 3W (12V - 24VDC)

 

 

 

PV: high luminance LED screen with 4 digits of height

 

9.9mm displayed in red

Characters

 

SV: high luminance LED screen with 4 digits of height

 

 

8.0mm displayed in green

 

 

Display accuracy

±0.2%FS 0.1ºC(1000ºC); 1ºC(1000ºC)

 

 

Sampling period

0.5 seconds

 

 

Temperature

0-50ºC

compensation

 

 

 

 

Relay output: AC 250V 3A (resistive load)

 

 

Control output

Voltage output (for driving SSR): 12VDC, 30mA DC

 

Maximum load: 600Ω

 

 

 

 

Electrical endurance of relay: 100,000 times

 

 

Alarm output

Relay output: AC 250V 3A (resistive load)

 

Relay output: AC 250V 3A (resistive load)

 

 

 

Weight

About 140g

 

 

Working temperature

-10 - 55ºC (No ice or moisture condensation)

 

 

Working humidity

RH 35-85%

 

 

Storing temperature

-25 - 65ºC (No ice or moisture condensation)

 

 

2.Models and specifications

Table 1: Product models and specifications

Model

Control output

Voltage

 

 

 

ITC-100VH

SSR control output

AC 100-240V

 

 

 

ITC-100RH

Relay control output

AC 100-240V

 

 

 

ITC-100VL

SSR control output

AC/DC 12-24V

 

 

 

ITC-100RL

Relay control output

AC/DC 12-24V

 

 

 

3.Diagram and installing size (unit: mm)

Figure 1: Shell Size

Figure 2: Mounting Bracket

Figure 3: Panel Cutout

3.1Insert temperature controller into the mounting hole in the panel, then put on the fixer from the rear and hold it temporarily, make sure there is no gap among temperature controller, panel and fixer. After that, fix the temperature controller with attached two bolts of the fixer under torque of 0.29N to 0.39N.

3.2Make sure the surrounding temperature is within the stipulated temperature range, especially when there are two or more temperature

controllers.

4.Wiring diagram

Figure 4:Wiring diagram

 

© 2015 Inkbird Inc. All rights reserved.

2

www.ink-bird.com, CS@ink-bird.com

4.1 Connecting sensors

Please refer to the input sensor reference table to select sensor type and set the code. The default setting of sensor type is type K thermocouple. If other type

sensor was adopted, it’s a must to reset the configuration.

If error occurred when some thermocouples are used in different environments, press SC to calibrate as per the detailed stipulation in this manual.

4.1.1 Thermocouple

#3 and #4 terminals are for connecting thermocouple. No inverse connection of positive pole and negative pole are allowed. For common thermocouples, positive pole is red, while negative pole is blue or green. If the poles were connected inversely, the measured value will be displayed inversely on the screen.

4.1.2 Dual lines PT100 sensor

#3 and #4 terminals are the input ports for dual lines PT100 sensor, at the same time #4 and #5 terminals should be connected together.

4.1.3 RTD sensor

When connecting three lines RTD sensor, #3 terminal is for red wire, #4 and #5 are for other two blue lines. For some sensors, #4 and #5 terminals should be connected together.

4.2 Power supply connection

#9 and #10 terminals are for connecting power supply, polarity is indifferent when

connecting. Before installation, it’s a must to confirm the compliance of the input

voltage to product specification, otherwise, there will be risks of abnormal usage, electric shock and fire.

4.3 Connection for control signal output

4.3.1The output driving voltage and current of Model ITC-100V are 12VDC and 30mA respectively, while #6 output terminal is for negative pole, and #8 terminal

is for positive pole. It can drive SSR (Solid-state replay). Please note that the

positive pole and negative pole shouldn’t be connected inversely.

4.3.2Model ITC-100R output relay control signals. COM7 is public port, COM6(NC) is normally closed, COM8 (NO) is normally opened. It could directly control load of AC250V, <3A; for controlling load of AC250V, >3A, external high capacity controller is needed.

4.4 Connection for alarm control

Alarm is controlled by relay signals. COM12 (COM) is public port, COM1 is normally closed, COM11 is normally opened, maximum load is AC250/3A (resistive load).

5. Panel instruction

 

 

 

PV window displays

 

 

 

measured value or set functional symbols

 

 

 

 

 

SV window displays

 

 

 

 

 

 

setting value or set value to be read

 

 

 

 

 

 

Working indicating light

 

 

 

 

 

 

OUT: Indicating control signal output

 

 

 

 

 

 

AL1: Indicating AL1 alarm

 

 

 

AL2: Indicating AL2 alarm

Figure 5

 

 

RUN: Manual indication

“INCREASE” key: when setting value, press“ ” key to increase

value,

keeping this key to be pressed can increase value quickly.

“DECREASE”key: when setting value, press “ ” key to decrease

value, keeping this key to be pressed can decrease value quickly. “MOVE“ key: when setting temperature value or parameters,

use this key to move cursor to required numerical position. “SELF-TUNING” key: when in normal display mode, long

press this key for over 2 seconds to start or stop self-tuning. “SWITCHING” key: when in normal display mode, press this key for less than 1 second to switch automatic and manual mode.

“SET” key: when in normal display mode, press this key to view setting value for control signal output; long press for over 2 seconds to enter parameters setting mode.

6.Operation instruction

6.1Display status

After power on, the instrument will conduct self-tuning, then enter measuring

and monitoring status automatically. PV window displays current measured

value, while SV window displays setting value; If “orAL” was displayed

alternately between PV and SV windows, it means input value exceeded measuring range (or sensors in open loop), or input setting is incorrect. When there was alarm output, SV window will alternately display characters related to the alarms:

HiAL(alarm for high limit),LoAL(Alarm for low limit), dHAL(alarm for plus deviation),dLAL(alarm for minus deviation).

6.2 View output value

Press “SET” key (no longer than 1 second), if SV window displays character “A”(for instance), it indicates automatic control mode, while if the displayed character is “M” (for instance: ), it indicates the manual control mode.

6.3 Automatic/Manual control switch

Press “«” key (no longer than 1 second), the temperature controller can

switch between automatic and manual control mode without interference to the operation. Under automatic control mode, RUN indicating light will off; and under manual control mode, RUN indicating light will on.

(remarks: if the running status of the function setting is “2: forbid manual mode”, above operation is invalid).

6.4 Value setting

When SV window displays setting value, press “ ” key (“ ” key) to increase (decrease) setting value. Press “«” key to move cursor to required numerical position. Keeping “ ” key or “ ” key to be pressed could increase or

decrease the value quickly.

6.5 Launch self-tuning function

When use the instrument for the first time, it’s a must to use the self-tuning

function of the instrument to determine control parameters (M50, P and t)

for an ideal control effect. Press “«” key for over 2 seconds, then the SV window will display characters “A” and “T” alternately, and the system will

enter self-tuning mode. When self-tuning, the temperature controller will conduct digital adjustment. After oscillation for 2 to 5 times, the instrument will automatically set the PID control parameters (parameters M50, P and T). After self-tuning, the system will return to PID automatic control mode.

During self-tuning, press “«” key for over 2 seconds to cancel self-tuning, then the characters “AT” displayed in SV window will disappear.

Attentions: for temperature controller which had run self-tuning before,

it’s a must to set parameter CtrL as “2” before launching another self-tuning (please refer to section “parameters setting and definition” in this manual

for detailed operation). The control parameter value will vary according to

setting temperature, therefore, it’s a must to run self-tuning with the most

frequently used setting value of the system. If the setting value often

changes, run self-tuning with the middle value of setting values.

 

© 2015 Inkbird Inc. All rights reserved.

3

www.ink-bird.com, CS@ink-bird.com

6.7 Parameters setting

Table 2: parameters setting and definition

Parameter

Definition

Value range

Unit

Default

Remarks

 

 

 

 

 

 

HIAL

Upper alarm limit

-1999~+9999

1

9999

See 6.8.1

 

 

 

 

 

 

LoAL

Lower alarm limit

-1999~+9999

1

-9999

See 6.8.1

 

 

 

 

 

 

dHAL

Deviation high alarm

0~9999

1

9999

See 6.8.1

 

 

 

 

 

 

dLAL

Deviation low alarm

0~9999

1

9999

See 6.8.1

 

 

 

 

 

 

dF

Hysteresis band

0~200.0

0.1

0.3

See 6.8.3

 

 

 

 

 

 

 

 

0: On/OFF

 

 

 

CtrL

Control mode

1,3: PID

 

3

See 6.10.2

 

 

2: Sel-turning

 

 

 

 

 

 

 

 

 

M50

Integral Time

0~9999

0.1

1000

See 6.11.3

 

 

 

 

 

 

P

Differential

0~9999

0.01S/

500

See 6.11.2

6.6 Workflow for setting

After instrument powered on and run self-inspection, press “SET” key for over 2 seconds to enter parameters setting mode. User can press “ ”

key(or “ ” key) to set the value. After value set, press “SET” key to

confirm and go for setting for another function. Then repeat above operation, till all the functions are configured OK.Quit setting mode, and enter PV/SV monitoring mode.

Attentions: if parameters were changed during parameters setting mode, the temperature controller will save the change if there is no further operation for over 10 seconds, and return to PV/SV monitoring mode.

t

Hysteresis time

1~9999

 

second

120

See 6.11.3

 

 

 

 

 

 

 

Ctl

Control period

1~120

 

second

4

See 6.11.4

 

 

 

 

 

 

 

Sn

Input sensor

0~42

 

 

0

See 6.9.1

 

 

 

 

 

 

 

diP

decimal point position

0~3

 

 

1

See 6.9.2

 

 

 

 

 

 

 

diL

Displayed value for low

-1999~+9999

 

1 Digital

0

See 6.9.3

limit

 

 

 

 

 

 

 

diH

Displayed value for high

-1999~+9999

 

1 Digital

1000

See 6.9.3

limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SC

Sensor Calibration

-199~+999

 

 

0

See 6.9.5

 

 

 

 

 

 

 

 

 

0/2time proportion

 

 

 

oP1

Output mode

10-10mA

 

0

See 6.10.1

 

 

 

 

 

 

 

 

 

 

 

 

Opl

Low limit of output

0~220

 

1%

0

See 6.10.1

 

 

 

 

 

 

 

Oph

High limit of output

0~220

 

1%

100

See 6.10.1

 

 

 

 

 

 

 

ALP

Alarm definition

0~31

 

 

0

See 6.8.2

 

 

 

 

 

 

 

 

System functions

2:Heater

 

 

 

CF

 

 

 

2

See 6.8.4

selection

3:Cooler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Addr

Communication address

0~63

 

 

1

See 6.12.1

 

 

 

 

 

 

 

Baud

Communication baud

0~4800

 

 

9600

See 6.12.2

rate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dl

Digital filtering

0~20

 

 

0

See 6.9.4

 

 

 

 

 

 

 

 

0: manual

 

 

 

run

Automatic/Manual

1: automatic

 

2

 

status

 

 

 

 

 

 

 

 

 

 

2: No manual

 

 

 

 

 

 

 

 

 

 

LOC

Permission of revising

0~999

 

 

40

See 6.14

parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EP1 EP8

8 definitions for field

Select Any

 

 

none

See 6.13

parameter

Parameters from it

 

 

 

 

 

Press SET 3S to enter Setting Mode

HIAL:Alarm value for high limit

SET

LOAL:Alarm value for low limit

SET

dHAL:Deviation high alarm

SET

dLAL:Deviation high alarm

SET

dF:Return difference

SET

CtrL:Control mode

SET

M50:Integral Time

SET

P:Rate

SET

t:Hysteresis time

SET

Ctl:Control period

SET

Sn:Input sensor

SET

diP:decimal place

SET

diL:Displayed value for low limit

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

diH:Displayed value for low limit

SC:Revise displayed value

oP1: Output mode

Opl:Low limit of output

Oph:High limit of output

ALP:Alarm definition

CF:System functions selection

Addr:Communication address

Baud:Communication baud rate

dl:Digital filtering

run:Running status

LOC:Permission of revising parameter

EP1-EP8:8 definitions for field parameter

Figure 6:Workflow for setting

 

© 2015 Inkbird Inc. All rights reserved.

4

www.ink-bird.com, CS@ink-bird.com

6.8Parameters related to alarm output: “HiAL, LoAL, dHAL, dLALdF, ALP, CF”

6.8.1Alarm parameters: "HiALLoALdHALdLAL". These parameters are for setting the alarm function of the instrument. When there is alarm condition, the system will output alarm signals to drive alarm relay to act (normally opened contact close/normally closed contact open), and alternately display the alarm reasons in the bottom screen. The alarm will be dismissed once the fault is fixed. Alarm conditions are as following:

HiAL: alarm when measured value is larger than HiAL (PV>HiAL).

LoAL: alarm when measured value is smaller than LoAL (PVLoAL).

dHAL: alarm when plus deviation is larger than dHAL (PV>SV+dHAL).

dLAL: alarm when minus deviation is smaller than dLAL (PV<SV-dLAL).

Generally, user don’t need 4 alarms in effect at the same time. For any

alarm not required, set it to the maximum value to avoid triggering it. For example, set HiAL=9999, LoAL=-1999, dHAL=9999, or dLAL=9999.

6.8.2 Defining parameter for alarm"ALP"

Table 3: defining alarm function

Alarm output

Alarm type

ALP

 

 

 

 

Upper alarm limit

0

 

 

 

AL1

Lower alarm limit

0

 

 

Deviation high alarm

0

 

 

 

 

 

Deviation low alarm

0

 

 

 

 

Upper alarm limit

1

 

 

 

AL2

Lower alarm limit

2

 

 

Deviation high alarm

4

 

 

 

 

 

Deviation low alarm

8

 

 

 

Above are part of common ALP setting. The setting range is 0 - 31. It defines the output position of 4 alarms -- HiALLoALdHAL

dHAL. It’s defined by following formula:

ALP=A×1+B×2+C×4+D×8+E×16

When A=0, HiAL alarm is output by AL1;

When A=2, HiAL alarm is output by AL2;

When B=0, LoAL alarm is output by AL1;

When B=2, LoAL alarm is output by AL2;

When C=0, dHAL alarm is output by AL1;

When C=1, dHAL alarm is output by AL2;

When D=0, dHAL alarm is output by AL1;

When D=1, dHAL alarm is output by AL2;

When E=0, SV screen will display alternately the alarm symbols, enabling user to know the reasons for alarm quickly;

When E=1, SV screen won’t display alternately the alarm symbols

(except orAL)

Alarm for input exceed measurable range (orAL) could occur when there are improper sensor specification setting, input disconnected or short circuit. If such alarm occurred, the instrument will stop control, and keep the output value as stipulated by parameter oPL. No setting is needed for orAL.

6.8.3 Hysteresis Band (Dead Band) parameter "dF"

For avoiding alarm signals caused by input value fluctuation, and consequently malfunction, the instrument has return difference parameter dF (also called as non-sensitive zone, dead zone, or hysteresis). For example, the influence of dF parameter: assume HiAL value is 800 , dF value is 2.0, then only when the measured temperature is larger than 802(HiAL+dF), the instrument enters HiAL alarm status. And only when the measured temperature is lesser than 798(HiAL-dF), the alarm will be dismissed.

6.8.4 Function parameter "CF"

Parameter CF is for selecting some system functions: when CF=2,

it’s heating control; when CF=3, it’s refrigeration control.

6.9Parameters related to input “ Sn, diP, diL, diH, DL, Sc” 6.9.1 Sensor type input “Sn”

Table 4: sensor input code and measuring range

Sensor type

Input

Code

Measuring range

 

 

 

 

 

K

0

-501300ºC

 

 

 

 

 

S

1

-501700ºC

 

 

 

 

 

WRe

2

-02300ºC

 

 

 

 

thermocouple

E

3

-2000350ºC

 

 

 

J

4

01000ºC

 

 

 

 

 

 

T

5

01000ºC

 

 

 

 

 

B

6

01800ºC

 

 

 

 

 

N

7

01300ºC

 

 

 

 

Copper resistor

Pt100

20

-50150ºC

 

 

 

 

Platinum resistor

Cu50

21

-200600ºC

 

 

 

 

6.9.2 Decimal point position “diP”

Decimal position “diP” is for selecting displaying accuracy. This setting is only

for display. The internal measuring accuracy is fixed to be 0.1. When diP=0, it means the temperature display accuracy is 1.

When diP=1, 2 or 3, it means the temperature display accuracy is 0.1. When the temperature display accuracy is set to be 0.1, while the measured temperature is lower than 1,000, the temperature will be displayed with accuracy 0.1; when the measured temperature is higher than 1,000, the temperature will be displayed with accuracy 1.

Changing diP parameter can only influence the display, there is no influence to the measuring accuracy.

6.9.3 Definition parameters "diH" and "diL" for linear input range

Linear input includes signals such as current: 0-20mV, 0-60mV;

voltage: 0-1V, 0-5V; resistance: 0-80Ω, 0-400Ω. The displaying value

range for the signals is -1999 - 9999 (decimal position could be set by diP). Parameters diH and diL are used to define the display range of linear input.

6.9.4 Filtering parameter “dL”

ITC-100 has in-built digital filtering system. When the displayed value is not stable due to input interference, use digital filtering to smooth it. dL=0-20, the larger the dL value, the measured value will be more stable, but respond will be more dull. When the instrument is interfered at field, gradually increase the dL value till the instant variation of measured value

is within 2-5 unit. When verifying the instrument, it’s a must to set dL as 0

to improve responding speed.

6.9.5 Amendment parameter “Sc”

Parameter “Sc” is for offset amendment for input to compensate the

deviation of sensor or input signal. For thermocouples, if there is deviation

at the cold compensation, use parameter “Sc” to amend.

For example, assume input signal is constant (500), and Sc value is

0.0, then the measured temperature is 500.0; while Sc value is 10.0, the measured temperature is 510.0. The default value of Sc is 0.

This parameter shouldn’t be amended unless there is need to calibrate

the measurement.

6.10 Parameters related to control output “oPIoPLoPHCtrL”

6.10.1Output mode parameters "oPI", "oPL" and "oPH" are used for limiting output

oPI is the mode of main output signal; oPL and oPH are the output low limit and high limit respectively.

When oPI=0, main output mode is time proportioning output (professional

PID adjustment) or digital adjustment. Models with SSR, relay, and zero-crossing triggering silicon should set oPI=0.

When oPI=1, output mode is continuous output (for models with linear

 

© 2015 Inkbird Inc. All rights reserved.

5

www.ink-bird.com, CS@ink-bird.com

current output). Output current are 0-10mA and 2-40mA.

When oPI=2, output mode is time proportioning output, and AL1 act as output synchronizing with main output. Under this mode, the AL1 of the

instrument can’t be used to output alarm signals as it’s used as output. Only AL2 is available for alarm signals (refer to 6.8).

oPL and oPH are the output low limit and high limit. Attentions: the setting of oPI should be in accordance with the module of main output.

When oPI=1 (current output), oPL and oPH are as following: 0-10mA output: oPL=0, oPH=100

4-20mA output: oPL=40, oPH=200

Example for nonstandard output current: 2-8mA output: oPL=20, oPH=80. oPI=0,2 (time proportioning output). Time proportioning output controls

the ratio of open and close of relay (or ratio of high and low voltage output of SSR) in a fixed period to realize output variation. Time proportioning output could be regarded as a square wave, its period is equal to control period Ctl. Output value is proportional to the duty ratio of square wave, varying from 0% to 100%. Users can use oPL and oPH to limit the output range of time proportioning output. For example, to limit the output within range 20%-60%, set oPL=20, oPH=60. Generally, the default setting of time proportioning output is oPL=0, oPH=100, that is, no output limitation.

(wave when output is 40% and 60%)

Figure 7 diagram of time proportioning output

6.10.2 Adjustment mode parameter "CtrL"

ITC-100 allows digital adjustment or professional PID adjustment. Select it by CtrL parameter.

When CtrL=0, adopt digital adjustment (ON-OFF). It’s only for

applications where the requirements are not strict.

When CtrL=1, adopt professional PID adjustment. It’s an improvement

based on PID adjustment and fuzzy adjustment, suitable for various

objects, and well control on fast changing objects and hysteresis. It’s

the default setting when product leaving factory. Under this setting,

self-tuning could be launched by panel operation.

When CtrL=2, launch self-tuning. It’s same operation as launching

self-tuning by panel operation. If another self-tuning is needed after self-tuning, set CtrL as 2 to re-launch self-tuning.

When CtrL=3, adopt professional PID adjustment. After self-tuning, the instrument will apply such setting. Under this setting, no self-tuning is allowed from panel operation, thus to avoid maloperation to launch self-tuning.

6.11PID control parameters related to self-tuning “M50, P, t” and functional parameter “CtL”

PID control parameters M50, P and t are the control parameters for professional PID adjusting algorithm. M50, P, and t are determined by self-tuning. This instrument adopted the latest professional PID adjustment which is a new algorithm enhanced with fuzzy logic. Following are the definition of each parameter.

6.11.1 Holding parameter "M50"

M50 defines the deviation for measured value when the object is stable, and the output value is 50% (when oPI=1, the current is 5.0mA). For example, for finding the best M50 value of a electric furnace, assume the output is keeping at 50%, the temperature of the electric furnace in

stable stage is 700, while when the output is 0%, the temperature of electric furnace is room temperature 25, then M50 (optimal value) is 700-25=675.

M50 is mainly for adjusting the integral action of adjusting algorithm. The smaller the M50, the strong the integral action. The larger the M50, the weak the integral action (integral time will increase). But when M50=0, system will cancel integral action.

6.11.2 Rate parameter "P"

P is inversely proportional to the measurement variation when the output is

100%. It’s definition is as following.

P= 100÷increased measuring value per second, the unit is or 10 defined units (when linear input). For example, when the output is 100%, no heat dissipation, and the temperature of the electric furnace increases

1per second, then:

P=100÷1=100

P has influence to adjusting proportion and differential. When the P value increased, the adjusting proportion and differential action will increase proportionally; while when the P value decreased, the adjusting proportion and differential action will decrease proportionally. P has no influence to integral action. Set P=0 is equal to set P=0.5.

6.11.3 Hysteresis time "t"

For industrial control, the hysteresis effect of object system is the main factor which influences control effect. The larger the system hysteresis time, more difficult to achieve ideal control effect. Hysteresis time t is a new important parameter introduced into professional PID algorithm in comparing with PID algorithm. The instrument can conduct fuzzy logic operation according to parameter t to perfectly solve overshoot and oscillation, as well as achieve fastest respond speed. t is defined as the time needed for the electric furnace reaching 63.5% of its maximum heating rate when heating with a fixed power.

6.11.4 Function parameter "CtL"

CtL value can be set between 0.5-120 seconds (CtL value 0 is equal to 0.5 seconds). It reflects the operation speed of instrument control. For time proportioning output (triggering by SSR voltage/relay/control silicon), it represents the control period of the instrument; for linear current output,

it controls the output fluctuation (time constant for digital filter to output value). If CtL is far lesser than hysteresis time t (lesser than 1/5 - 1/10), there is no difference if changing CtL. For example, when hysteresis time t is 100 seconds, then the control effect will be same no matter CtL=0.5 seconds

or CtL=10 seconds. Principle for determining CtL:

a. When under time proportioning output, and using SSR or controlled silicon as output actuator, the control period could be short (generally 4 seconds) to improve control accuracy. When using relay open and close to control output, short control period will be harm to the lifetime of mechanical switch, so the control period is generally 20 seconds.

b. When the output is linear current, small CtL value can speed up the respond against intelligent adjustment, and improve control accuracy. But the large differential action may cause frequent change of output current. If the actuator is regulating valve, and there are frequent valve actions, enlarge CtL properly to slow down the valve action till it meet the requirement.

6.12 communication parameter “Addr, bAud”

6.12.1Parameter Addr defines the communication address of the instrument, its effective range is 0 - 63. Instruments in a same communication line should be set with different Addr to distinguish from each other.

6.12.2Parameter bAud defines the communication baud rate, its effective range is 300 - 4800 bit/s

 

© 2015 Inkbird Inc. All rights reserved.

6

www.ink-bird.com, CS@ink-bird.com

6.13 Field parameter "EP1 - EP8"

After setting the instrument, most parameters don’t need to be amended at field. Besides, operators generally don’t understand many parameters,

and there is risk of fault caused by wrong setting by operators.

Generally, intelligent instrument has parameter lock (Loc) function. Common parameter lock will lock all the parameters. Sometimes, certain parameters need to be amended or adjusted at field by the operators. For example, parameters such as alarm high limit or alarm low limit. In parameter table, EP1 - EP 8 are 8 field parameters for operators. The value of parameter EP is other parameters, such as HiAL and LoAL. When Loc=0 or 1,

selected parameters will be displayed, other parameters won’t be displayed

and amended. This function can speed up the amendment, and avoid important parameters (such as input and output parameters) been amended incorrectly.

There are maximum 8 field parameters available for parameter EP1- EP2. If field parameters are less than 8 (sometime none), they should be defined orderly from EP1 to EP8. Vacant field parameters are defined as nonE.

6.14 Permission for parameters “Loc”

Protection function Loc: when Loc is set as value except 2, 40, 808, the instrument only display the filed parameters (EP1 - EP8) and Loc. Only if set Loc as 2, 40 or 808, all the parameters can be amended.

When Loc=0, field parameters (EP1 - EP8)and temperature setting value can be amended.

When Loc=1, field parameters can’t be amended (except Loc).

When Loc=2, 40 or 808, all the parameters and temperature setting

value can be amended.

6.15 Common faults and handling methods

Table 5:Error and handling

Faults

Reasons

Handling methods

 

 

 

 

Wrong input

Check whether the input voltage is in

 

accordance with the specification of

 

voltage

 

the instrument

 

 

PV and SV

Power cable is

Check whether the power cable is

screen not work

not well

bad or wrongly connected

connected

 

 

 

Instrument fault

Contact manufacturer or dealer

 

 

 

 

Sensor fault

Check whether sensor is connected

 

correctly

 

 

orAL displayed

 

 

Wrong

Select correct graduation mark in

on the

graduation

accordance with input signal

instrument

mark selected

 

Wrong

 

 

connection for

Connect signal cable correctly

 

sensors

 

 

Wrong

Select correct graduation mark in

 

graduation

 

accordance with input signal

Wrong

mark selected

measured value

Wrong

 

 

connection for

Connect signal cable correctly

 

sensors

 

Malfunction of

Wrong setting

Refer to the alarm instruction in the

for control

user manual to selected required

relay

output

alarm mode

 

No control

Wrong wiring

Connect control output cable

output

for control

correctly

output

 

 

7. Wiring instruction

7.1 Directly control load by the internal relay of the instrument.

Figure 8:ITC-100RH Wiring diagram

Control the heater by the internal relay of the instrument, no external control circuit is needed. This mode is only applicable for heater whose maximum load is 250V/3A or 120V/6A.

The internal control of alarm is relay output control which controls the power supply of the speaker. User can use bulb to replace with the speaker as alarm.

7.2 Control the load via external contactor

Figure 9:ITC-100RH Wiring diagram

Instrument control output via external relay or contactor. With this method, the user can select external relay or contactor based on the power of heater, avoid output limitation of the internal relay of the instrument, and improve the lifetime of the instrument.

7.3 SSR control

Figure 10:ITC-100VH Wiring diagram

ITC-100VH’s output control signal is DC12V voltage for controlling external

SSR to control the heater. User can select SSR based on the power of the heater. SSR is a kind of electronic switch without contactor, which can be used for higher frequency control than relay, featuring more stable temperature control for heater and long lifetime.

 

© 2015 Inkbird Inc. All rights reserved.

7

www.ink-bird.com, CS@ink-bird.com

7.4 Solenoid valve or relay control

Figure 11:ITC-100RL Wiring diagram

ITC-100RL is generally used for low voltage devices. It’s a must to pay

attention to whether the power supply voltage and alarm voltage is within

the stipulated range when wiring.

7.5 Control load via external contactor (24V)

Figure 12:ITC-100RL Wiring diagram

ITC-100RL’s control mode is the same as figure 9. Please note that the

power supply for heater is high voltage(120VAC), the power supply for

instrument is 24VAC (low voltage).

8. Field application example

For example, the application of instrument for oven. Following example is based on ITC-100RH and ITC-100VH, the required temperature is 150 ºC, and the high limit is 160ºC.

Figure 13:ITC-100RH Wiring diagram

Figure 14:ITC-100VH Wiring diagram

Wiring steps:

1.Connect sensor: the sensor in figure 13 and 14 are both three lines RTD sensors. Their connection method are the same. Red wire is for COM3, other two blue wires are for COM4 and COM5 (two blue wires can exchange COM port with each other).

2.Connect alarm: ITC-100RH and ITC-100VH’s alarm control output are the same. COM12 is the power input port for alarm, which should connect with phase line (L). COM11 is alarm control output port, which should connect with alarm. The other line of the alarm should connect with the null line.

3.Connect heating tube: ITC-100RH controls heating tube by its internal relay. COM7 of the instrument connect with the power input port, which should connect with phase line (L). COM8 is the control output port, which should connect directly with the heating tube. The other wire of the heating tube should connect with null line (N); TC-100VH output DC12V voltage as control

signal, driving SSR to control heating tube. COM8 of the instrument output

positive voltage, which should connect with SSR’s positive pole; COM6 of the instrument output negative voltage, which should connect with SSR’s

negative pole. The polarity should not be inversely connected.

4.Connect power supply: the power supply port of the instrument are COM9 and COM10, which are for the phase line and null line respectively. A dual linked switch should be connected in front of power supply, and connect fuse in phase line(L). The wire used must be able to bear the load current, otherwise, there will be risk of accidents such as fire

For simple users, no need to master all instructions, as long as the parameters of the following parameters in the process to set up to get the ideal control effect, set up flow chart as below:

 

© 2015 Inkbird Inc. All rights reserved.

8

www.ink-bird.com, CS@ink-bird.com

Power On

Initial display

 

 

 

 

 

 

 

 

Setting Alarm value for

 

 

 

high limit

Setting Control mode

 

Setting Input sensor

 

 

 

value

 

 

Setting Revise

 

 

displayed value

 

 

Setting Alarm

 

 

 

definition

 

 

Setting System

 

functions selection

Setting Permission of

 

revising parameter

8 definitions for field parameter

Setting target temperature SV=150

SET

Setting HIRL=160, more setting of alarms, please check 6.8.1

SET *if don't need to set this parameter, press SET key to run into next setting.

Keep the Default value

SET

Sn=20 (CU=20, more detail please check 6.9.1)

SET

Keep the Default value

SET

Keep the Default value

SET

Keep the Default value. 2:Heater, 3:Cooler

SET

Keep the Default value

SET

Keep the Default value

SET

Figure 15:Workflow of sample

 

© 2015 Inkbird Inc. All rights reserved.

9

www.ink-bird.com, CS@ink-bird.com