Navigating the complexities of energy efficiency compliance in California, the NRCC-ELC-01-E form plays a pivotal role for professionals involved in the design and construction of nonresidential buildings. This form serves as a Certificate of Compliance under the 2016 CA Building Energy Efficiency Standards, specifically focusing on the Electrical Power Distribution aspect of a project. It requires detailed information about the project, including its name, address, the climate zone in which it's located, and specifics about the conditioned and unconditioned floor areas, in addition to the type of building and the phase of construction. The form is designed to ensure that the electrical power distribution system of a nonresidential building adheres to the state's stringent standards for energy efficiency, ranging from service electrical metering to the separation of electrical circuits for better energy monitoring and control. The nuanced requirements detailed in this form, such as voltage drop compliance, circuit controls for 120-Volt receptacles, and specialized controls for various types of buildings, highlight California's commitment to reducing energy consumption and promoting sustainability. By fulfilling the criteria laid out on each page of the NRCC-ELC-01-E form, project teams contribute to more energy-efficient buildings that not only comply with current legislation but also pave the way for a more sustainable future.
Question | Answer |
---|---|
Form Name | Nrcc Elc 01 E Form |
Form Length | 6 pages |
Fillable? | No |
Fillable fields | 0 |
Avg. time to fill out | 1 min 30 sec |
Other names | 2013 NRCC ELC 01 E Disaggregation_of_Electrical _Circuits elc 01 form |
STATE OF CALIFORNIA
ELECTRICAL POWER DISTRIBUTION
CALIFORNIA ENERGY COMMISSION |
|
|
|
CERTIFICATE OF COMPLIANCE |
|
|
|
Electrical Power Distribution |
(Page 1 of 6) |
Project Name:
Date Prepared:
General Information
Project Address: |
|
|
|
|
Climate Zone: |
|
Conditioned Floor Area: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unconditioned Floor Area: |
|
|
|
|
|
|
|
|
Building Type: |
|
Nonresidential |
|
|
Hotel/Motel |
||
|
|
Schools |
|
Relocatable Public Schools |
|
|
|
Phase of Construction: |
|
New Construction |
|
Addition |
|
Alteration |
In the table below identify all applicable construction documents that specify the requirements for the scope of responsibility reported by this certificate. Use additional pages as needed to list all construction documents related to compliance of Section 130.5.
|
|
|
|
|
|
Indicate which |
|
|
|
|
|
|
|
|
subsection of |
|
|
|
|
|
|
|
|
|
|
|
|
Document Title / Descriptions |
|
|
|
|
Section 130.5 is |
|
|
|
|
|
|
|
|
|
|
|
|
|
Document Sheet # |
|
|
related to the |
|
|
|
Document Number |
(include description information for Table or |
|
|
|
|
|
||
|
or Page # |
|
|
document (e.g. |
|
|
||
|
Schedule if it contains compliance information) |
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
130.5(a) for |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
service electrical |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
metering) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
January 2016
STATE OF CALIFORNIA
ELECTRICAL POWER DISTRIBUTION
CALIFORNIA ENERGY COMMISSION |
|
|
|
CERTIFICATE OF COMPLIANCE |
|
|
|
Electrical Power Distribution |
(Page 2 of 6) |
Project Name:
Date Prepared:
Document Number
Document Title / Descriptions
(include description information for Table or Schedule if it contains compliance information)
Document Sheet #
or Page #
Applicable
subsection of
Section 130.5
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance |
January 2016 |
STATE OF CALIFORNIA
ELECTRICAL POWER DISTRIBUTION
CALIFORNIA ENERGY COMMISSION |
|
|
|
CERTIFICATE OF COMPLIANCE |
|
|
|
Electrical Power Distribution |
(Page 3 of 6) |
Project Name:
Date Prepared:
A. Service Electrical Metering
Check one of the three boxes below if the electrical power distribution system is in compliance with Section 130.5(a).
For newly installed electrical service in newly constructed buildings, Service Electrical Metering is required according to Section 130.5(a). Fill out Column 1 thru 6 of table below.
For new or replacement electrical service equipment in existing buildings, Service Electrical Metering is required according to Section 141.0(b)2Pi. Fill out Column 1 thru 6 of table below.
EXCEPTION to Electrical Service Metering: Service or feeder for which the utility company provides a metering system that indicates instantaneous kW demand and kWh for a
Fill out a separate line for each electrical service that is connected to the building. If additional table space is needed for electrical service information, submit additional page with the information.
|
Electrical |
Electrical Service Schedule |
Service |
|
Rating |
01 |
02 |
Electrical Service |
|
Designation/Location/Description |
kVA |
|
Metering Capabilities |
|
Exception to |
||
(check all that are present) |
130.5(a) |
||||
03 |
|
04 |
05 |
06 |
07 |
Instantaneous (at the time) |
kW |
Historical peak (kW) |
Tracking kWh for a user- definable period |
kWh per rate period |
Utility metering system |
Field Inspector
08
Check that the
metering complies
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance |
January 2016 |
STATE OF CALIFORNIA
ELECTRICAL POWER DISTRIBUTION
CALIFORNIA ENERGY COMMISSION |
|
|
|
CERTIFICATE OF COMPLIANCE |
|
|
|
Electrical Power Distribution |
(Page 4 of 6) |
Project Name:
Date Prepared:
B. Separation of Electrical Circuits for Electrical Energy Monitoring
Check all boxes below if the electrical power distribution system is in compliance with Section 130.5(b).
The electrical power distribution system meets the separation of electrical circuits for electrical energy monitoring requirement of Section 130.5(b). The electrical power distribution systems is designed so that measurement devices can monitor the electrical energy usage of load types according to TABLE
Describe the electrical power distribution system installed and the compliance method chosen in meeting the requirement of Section 130.5(b). Use the space below to include the information. Examples of compliance methods are detailed in Nonresidential Compliance Manual Chapter 8.
Fill out Column 1 thru 3 with the compliance information.
General information |
Electrical Power Distribution System information and Method of |
Electrical Service |
Enforcement |
|
compliance |
Rating |
Agency |
||
|
||||
|
|
|
|
|
01 |
02 |
03 |
04 |
|
|
|
|
|
|
Electrical Service |
Describe the electrical power distribution system installed and the |
|
Check that the |
|
Designation/Location/Descrip |
kVA |
|||
compliance method used. |
system complies |
|||
tion |
|
|||
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Field Inspector Notes:
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance |
January 2016 |
STATE OF CALIFORNIA
ELECTRICAL POWER DISTRIBUTION
CALIFORNIA ENERGY COMMISSION |
|
|
|
CERTIFICATE OF COMPLIANCE |
|
|
|
Electrical Power Distribution |
(Page 5 of 6) |
Project Name:
Date Prepared:
C. Voltage Drop
Check all boxes below if the electrical power distribution system is in compliance with Section 130.5(c).
The electrical power distribution system meets the voltage drop requirement of Section 130.5(c). The maximum combined voltage drop on feeder conductors and branch circuit conductors to the farthest connected load or outlet, do not exceed 5%.
Voltage drop calculation documents showing compliance to Section 130.5(c) are submitted as part of the compliance document submittal.
Enforcement Agency
Check that the system
complies
D. Circuit Controls for |
Field Inspector |
|
Check one or more boxes below for applicable requirements of Section 130.5(d) for the electrical power distribution |
Cehck that the system |
|
system. |
complies |
|
|
|
|
The control is capable of automatically shutting OFF the controlled receptacles when the space is typically |
|
|
unoccupied, either at the receptacle or circuit level. For the automatic time switch control, it incorporates an |
|
|
override control that allows the controlled receptacle to remain ON for no more than 2 hours when an override |
|
|
is initiated and an automatic holiday |
||
|
||
resumes the normally scheduled operation. Countdown timer switches are not be used to comply with the |
|
|
automatic time switch control requirements. The controls meet the requirement of Section 130.5(d)1. |
|
|
|
|
|
There is at least one controlled receptacle within 6 ft from each uncontrolled receptacle. Where receptacles are |
|
|
installed in modular furniture in open office area, at least one controlled receptacle is installed at each |
|
|
workstation. The receptacles meet the requirement of Section 130.5(d)2. |
|
|
|
|
|
There are installed split wired receptacles with at least one controlled and one uncontrolled receptacle. Where |
|
|
receptacles are installed in modular furniture in open office area, at least one controlled receptacle is installed |
|
|
at each workstation. The receptacles meet the requirement of Section 130.5(d)2. |
|
|
|
|
|
Permanent and durable marking for controlled receptacles or circuits to differentiate them from uncontrolled |
|
|
receptacles or circuits is provided. The markings meet the requirement of Section 130.5(d)3. |
||
|
||
|
|
|
For hotel and motel guest rooms, there are controlled receptacles for at least |
|
|
receptacles in each guest room. Electric circuits serving controlled receptacles in guestrooms are installed to |
|
|
have captive key controls, occupancy sensing controls, or automatic controls so the power is switched off no |
|
|
longer than 30 minutes after the guest room has been vacated. The receptacles meet the requirement of |
|
|
Section 130.5(d)4. |
|
|
|
|
|
Receptacles that are only for the following purposes are excepted from Section 130.5(d): |
|
|
|
||
|
||
|
||
copy rooms. |
|
|
|
||
|
||
hours per day/365 days per year, and are marked to differentiate them from other uncontrolled |
|
|
receptacles or circuits. |
|
|
|
|
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance |
January 2016 |
STATE OF CALIFORNIA
ELECTRICAL POWER DISTRIBUTION
CALIFORNIA ENERGY COMMISSION |
|
|
|
CERTIFICATE OF COMPLIANCE |
|
|
|
Electrical Power Distribution |
(Page 6 of 6) |
Project Name:
Date Prepared:
DOCUMENTATION AUTHOR’S DECLARATION STATEMENT
1.I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name:
Documentation Author Signature:
Company:
Signature Date:
Address:
CEA/ HERS Certification Identification (if applicable):
City/State/Zip:
Phone:
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1.The information provided on this Certificate of Compliance is true and correct.
2.I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible designer).
3.The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4.The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5.I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the building owner at occupancy.
Responsible Designer Name:
Responsible Designer Signature:
Company :
Date Signed:
Address:
License:
City/State/Zip:
Phone:
CA Building Energy Efficiency Standards - 2016 Nonresidential Compliance |
January 2016 |