The Niceic Electrical Certificate form serves as a critical document within the realm of electrical installations, playing an essential role in ensuring the safety, compliance, and oversight of electrical work. This comprehensive form is issued under the stringent guidelines of the British Standard 7671 - Requirements for Electrical Installations, ensuring that every aspect of an electrical installation project is meticulously documented and certified by approved contractors or conforming bodies enrolled with NICEIC. The form carries details about the client and the specifics of the electrical installation, including the scope of work, the design, construction, inspection, and testing phases, encapsulating the meticulous nature of the work carried out. It emphasizes the importance of adherence to the BS 7671 regulations, with the form providing spaces for detailing any departures from these stipulations. Responsibility for each phase of the project is clearly delineated, with signatures from the responsible persons, thereby underscoring the accountability and precision expected in such critical work. Furthermore, the form includes specific sections for recording the electrical supply characteristics, earthing arrangements, and protective measures against electric shock, among other details, ensuring a thorough review and assessment of the electrical installation's safety and compliance. This certificate thereby becomes an indispensable document, validating the integrity and compliance of the electrical work with established standards, and serving as a tool for clients, contractors, and regulatory bodies to verify the safety and proficiency of electrical installations.
| Question | Answer |
|---|---|
| Form Name | Niceic Electrical Certificate |
| Form Length | 5 pages |
| Fillable? | No |
| Fillable fields | 0 |
| Avg. time to fill out | 1 min 15 sec |
| Other names | 18th edition test sheets, eicr certificate pdf, electrical test sheet example, electrical installation certificate template |
This certificate is not valid if the serial |
ICN2/0335772 |
|
number has been defaced or altered |
||
|
||
|
|
ELECTRICAL INSTALLATION CERTIFICATE
Issued in accordance with British Standard 7671 - Requirements for Electrical Installations by an
Approved Contractor or Conforming Body enrolled with NICEIC, Warwick House,Houghton Hall Park,
Houghton Regis,Dunstable,LU5 5ZX
DETAILS OF THE CLIENT
Client / |
Birmingham Airport Ltd, Property Services, Fourth Floor, Diamond House, Birmingham Airport |
Postcode: |
B26 3QJ |
|
Address: |
||||
|
|
|
DETAILS OF THE INSTALLATION |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The installation is: |
||||||||||||
Address: |
|
|
Room VH50, Second Floor, Viscount House, Birmingham Airport |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Postcode: |
B26 3QJ |
|
|
New |
|
|
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
Extent of the |
|
|
Installation of consumer unit, supply cable, lighting and power circuits in Room VH50 as specified in contract No. ES1476 only. |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
An |
á |
|
||||||||||||||||||||||||||||||||||||||
installation |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
addition |
|
|||||
covered by this |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
certificate: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
An |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
alteration |
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
DESIGN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
I/We, being the person(s) responsible |
for the design of the electrical |
installation |
|
(as |
indicated |
by |
|
my/our signature(s) |
|
below), |
particulars |
of |
which |
are |
|
|
||||||||||||||||||||||||||||||||||||
described above, having exercised reasonable skill and care when carrying |
out the design, hereby CERTIFY |
that |
the |
design |
work |
for which I/we have been |
|
|
||||||||||||||||||||||||||||||||||||||||||||
responsible is, |
to |
the best of my/our |
knowledge and |
belief, in |
accordance |
with BS |
7671 |
amended |
to |
|
|
|
|
January 2012 |
|
|
|
|
|
|
|
(date) |
|
|
|
|
|
|
|
|
||||||||||||||||||||||
except for the departures, if any, detailed as follows: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
Details of departures from BS 7671, as amended (Regulations 120.3,120.4): |
|
None noted |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
The extent of liabilty of the signatory/signatories is limited to the work described above as the subject of this certificate. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||
For the DESIGN of the installation: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
** (Where there is divided responsibility for the design) |
|
|
|||||||||||||||||||||||||||
Signature |
|
|
|
|
|
|
|
|
|
|
Date |
|
17/04/2012 |
|
|
|
|
|
|
|
Name (CAPITALS) |
|
D. LEE |
|
|
|
|
|
|
|
|
|
|
|
Designer 1 |
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
Signature |
|
|
|
|
|
|
|
|
|
|
Date |
|
17/04/2012 |
|
|
|
|
|
|
|
Name (CAPITALS) |
|
|
|
|
|
|
|
|
|
|
** |
Designer 2 |
|
|
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
CONSTRUCTION |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
I/We, being the person(s) responsible |
for the construction of the electrical |
installation |
(as |
indicated |
by |
my/our |
signature |
below), |
particulars |
of |
which |
are |
|
|
||||||||||||||||||||||||||||||||||||||
described above, having exercised reasonable skill and care when carrying out the construction, hereby CERTIFY that the construction work for which I/we have been |
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||
responsible is, |
to |
the best of my/our |
knowledge and |
belief, in |
accordance |
with BS |
7671 |
amended |
to |
|
|
|
|
January 2012 |
|
|
|
|
|
|
|
(date) |
|
|
|
|
|
|
|
|
||||||||||||||||||||||
except for the departures, if any, detailed as follows: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||
Details of departures from BS 7671, as amended (Regulations 120.3,120.4): |
|
None noted |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
The extent of liabilty of the signatory is limited to the work described above as the subject of this certificate. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||
For the CONSTRUCTION of the installation: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
Signature |
|
|
|
|
|
|
|
|
|
|
Date |
|
17/04/2012 |
|
|
|
|
|
|
|
Name (CAPITALS) |
|
R. SARTIN |
|
|
|
|
|
|
|
|
|
|
Constructor |
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
INSPECTION AND TESTING |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
I/We, being the person(s) responsible for the inspection and testing of the electrical |
installation (as indicated by my/our |
signatures below), particulars of |
which |
are |
|
|
||||||||||||||||||||||||||||||||||||||||||||||
described above, having exercised reasonable skill and care when carrying out |
the inspection and testing, hereby CERTIFY that the work |
for which |
I/we |
have |
been |
|
|
|||||||||||||||||||||||||||||||||||||||||||||
responsible is, |
to |
the best of my/our |
knowledge and |
belief, in |
accordance |
with BS |
7671 |
amended |
to |
|
|
|
|
January 2012 |
|
|
|
|
|
|
|
(date) |
|
|
|
|
|
|
|
|
||||||||||||||||||||||
except for the departures, if any, detailed as follows: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
Details of departures from BS 7671, as amended (Regulations 120.3,120.4): |
|
None noted |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||
The extent of liabilty of the signatory/signatories is limited to the work described above as the subject of this certificate. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||
For the INSPECTION AND TESTING of the installation: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
Signature |
|
|
|
|
|
|
|
|
|
|
Date |
|
17/04/2012 |
|
|
|
|
|
|
|
Signature |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Date |
17/04/2012 |
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Qualified |
|
|
|||
Name (CAPITALS) |
A. COPE |
|
|
|
|
|
|
Inspector |
|
|
|
|
Name (CAPITALS) |
|
A. COPE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SupervisorÚ |
|
|
||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
DESIGN, CONSTRUCTION, INSPECTION AND TESTING * |
|
|
|
|
* |
This box to be completed only where the design, construction, |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||||||||||||||||
|
|
|
|
|
inspection and testing have been the responsibility of one person. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||||
I, being the person |
responsible for the |
design, construction, |
inspection |
and |
testing |
of |
the |
electrical |
installation (as |
indicated |
by my |
signature below), particulars of which |
||||||||||||||||||||||||||||||||||||||||
are described |
above, |
having exercised |
reasonable skill |
and |
care |
when |
carrying |
out |
the design, |
|
construction, |
inspection |
and |
testing, |
hereby CERTIFY that the said work |
|||||||||||||||||||||||||||||||||||||
for which I have been responsible is to the best of my knowledge and belief, in accordance with BS 7671, amended to |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(date) |
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||||||
except for the departures, if any, detailed as follows: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||
Details of departures from BS 7671, as amended (Regulations 120.3,120.4): |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
The extent of liabilty of the signatory is limited to the work described above as the subject of this certificate. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||
For the DESIGN , the CONSTRUCTION and the INSPECTION AND TESTING of the installation: |
|
|
|
|
|
|
|
|
|
|
Reviewed by |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||||||||||||
Signature |
|
|
|
|
|
|
|
|
|
|
Date |
|
17/04/2012 |
|
|
|
|
|
|
|
Signature |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Date |
17/04/2012 |
|
|
|
|
||||||||||
Name (CAPITALS) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Name (CAPITALS) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Qualified |
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SupervisorÚÚ |
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ÚWhere the inspection and testing have been carried out by an Approved Contractor, the inspection and testing results are to be reviewed by the registered Qualified Supervisor. ÚÚ Where the design, the construction, and the inspection and testing have been the responsibilty of one person, the inspection and testing results are to be reviewed by the
registered Qualified Supervisor. |
Page 1 of |
5 |
Duplicate (To be retained by the contractor)
This form is based on the model shown in Appendix 6 of BS7671 (as amended).
Published by the NICEIC a part of the Ascertiva Group © Copyright The Electrical Safety Council (Jan 2008)
Please see the 'Notes for Recipients' on the reverse of this page