Residential HVAC Worksheet, Manual J / S Summary at a glance
What it is: Residential HVAC Worksheet, Manual J / S Summary, from Building Services & Civil Enforcement.
Where and when to file: Attach a complete gas pipe layout & sizing detail to the plan or permit application.
A filled-in Residential HVAC Worksheet, Manual J / S Summary example: a contractor fills in the heating part

How to fill out Residential HVAC Worksheet, Manual J / S Summary, box by box
Project and Location
Design Conditions

Provide both heating (htg) and cooling (clg) design temperatures.
Outside Dry Bulb and Inside Dry Bulb temperature data should be from Table 1 or Table 1A of ACCA Manual J.
If values are adjusted, please justify the adjustment. If inside or outside design conditions listed are not the same values listed in Manual J, explain why the different values were used.
Entering WB: assume no higher than 63 °f unless there is ventilation air or significant duct leakage or heat gain.
Design TD is the temperature difference between inside and outside design temperatures.
Infiltration

Infiltration calculations are based on the Construction Quality; note the method used on the summary.
Open firebox fireplaces that draw air from inside the home must be included, even if there is a 4” combustion air flex bring air into the fireplace; sealed, direct vent type fireplaces should not be counted.
Heat Loss and Heat Gain

Manual J Heat Loss is the whole house winter heat loss taken directly from the completed attached Load Calculation.
Heating airflow typically may be lower than cooling cfm; it is adjusted to insure the temperature rise across the heat exchanger falls within the range specified by the manufacturer.
Manual J Sensible Gain is the whole house summer heat gain taken directly from the completed attached Load Calculation.
Total Gain is the combined total of the sensible and latent gain.
SHR is the ratio of sensible heat gain to total heat gain: SHR = Sensible Heat Gain ÷ Total Heat Gain.
Recommended air flows: If SHR is under 0.80 select 350 cfm / ton; if SHR is between 0.80 & 0.85 select 400 cfm; if SHR is greater than 0.85, select 450 cfm / ton.
Note: This cfm is not the final cfm; additional adjustment may be required for Altitude.
Heating Equipment

List specific equipment to be used; this information is not required on the Load Calculation documents, however it must be provided here to verify equipment sizing against calculated loads.
The AFUE listed here will be compared to that listed on plans and on energy compliance documents, and it must also match the equipment actually installed in the home.
Sea Level Input is the listed input on the furnace label and in manufacturers' documentation.
Output is the amount of heat available for discharge into the conditioned space; it may be from manufacturer's performance data or calculated using input and furnace efficiency.
Altitude Adjusted Output is the actual output that will be attained after the furnace has been adjusted for efficiency and de-rated for altitude (typically 4% for every 1000' over sea-level, however 2% /1000' for many 90+ efficient furnaces). Some manufacturers may have different requirements, so adjustments should be made per their requirements. Calculations should be attached.
When comparing to heating load calculated, use the maximum adjusted output to verify the furnace is large enough and the lowest output to insure it is not too large.
If “adjusted output” is greater than 1.4 times the “total heating load”, please justify.
Cooling Equipment

Provide manufacturers comprehensive data for furnace, furnace blower and condenser, with capacities at design conditions highlighted.
Total capacity is the latent and sensible capacity at design conditions.
Latent capacity and Sensible capacity are the latent only and the sensible only capacity from the manufacturer's expanded data at design conditions.
Attach manufacturers' documentation or ARI report showing actual cooling capacity, and actual SEER using the components used this system; indoor air handler / furnace blower must be included in this documentation. Do not use ARI (ARHI) data for actual sizing.
List the exact model number for the evaporator coil used this system. If coil is from a different manufacturer than the condenser is used, provide data from both manufacturers verifying actual performance.
Provide the specific metering used, orifice or TXV (thermostat expansion valve); if the manufacturer has several options, list the option used.
If “cooling capacity” is greater than 1.15 times the “total heating load”, please justify.
More rules for Residential HVAC Worksheet, Manual J / S Summary
This friction rate (FR) calculated in Step 5 is the rate to be used with a duct calculator or a friction chart for the duct design on this project.
Attach at a minimum, a one line diagram showing the duct system with fittings, sizes, equivalent lengths through fitting and duct lengths.
Total effective length (TEL) = supply side TEL + return side TEL; FR = ((100 x ASP) / TEL).
For a boiler or furnace, enter the De-rated input rating (use .83); for a water heater, use .83 minimum.
If a manifold is used to connect the appliances on the horizontal, it shall be the same size as the vent.
Combustion air is computed at 1 in² per 3,000 Btu of input of all fuel burning appliances in the room.
Common questions about Residential HVAC Worksheet, Manual J / S Summary
How do I calculate the manual J load for an HVAC system?
The load information asked for on the summary must be taken from the actual load calculation completed on the project. Load must account for all factors such as loss building components as well as loss through infiltration, ventilation, and duct losses.
Who signs it?
By signing in Signature and entering the Date you certify that the information contained within this document is true, correct, and meets the requirements of the 2009 International Mechanical Code and International Fuel Gas Code.
What am I certifying when I sign?
To the best of my knowledge, I certify that the information contained within this document is true, correct, and meets the requirements of the 2009 International Mechanical Code and International Fuel Gas Code.
When is this form not the right one?
This sheet has been developed for Utah's dry climates; do not use it for other climate conditions. The load calculation must be calculated on a room basis. Room loads are a mandatory requirement for making Manual D duct sizing calculations.
Sources
[1] Residential HVAC Worksheet, Manual J / S Summary (Updated 12/2012), Salt Lake City Building Services & Civil Enforcement (the Official source link on this page).

