Printable Manual J Form PDF Details

A Printable Manual J Form can be found on the internet, and it is a valuable tool when sizing heating and cooling systems for a home. The form helps to ensure that the system is properly sized, which can help to save money on energy costs in the long run. Additionally, using a Printable Manual J Form can help to ensure that the warranty on the equipment remains valid. While many people may be hesitant to use a Printable Manual J Form, it is actually a very simple process that only takes a few minutes to complete. By following the instructions on the form, homeowners can rest assured that their heating and cooling system will be correctly sized.

The following are some specifics about printable manual j form. It is definitely worth taking the time to learn this before you start filling out your document.

QuestionAnswer
Form NamePrintable Manual J Form
Form Length4 pages
Fillable?No
Fillable fields0
Avg. time to fill out1 min
Other nameson line manual j form, blank manual j forms, manual j form, manual j pdf

Form Preview Example

Building Services & Civil Enforcement slcpermits.com

801-535-6000, fax 801-535-7750

451 South State Street, Room 215

PO Box 145490

Salt Lake City, Utah 84111

Salt Lake City, Utah 84114-5490

Office only

Updated 12/2012

BLD # Received by

Date Valuation

Residential HVAC Worksheet

Manual J / S Summary

NOTE: The load calculation must be calculated on a room basis. Room loads are a mandatory requirement for making Manual D duct sizing calculations. This sheet has been developed for homs built in Utah’s dry dimares- do not use for other climate conditions.

Design Information

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Project

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Location

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Design Conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Htg

Clg

 

 

Altitude

 

 

ft

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside db

 

 

°f

 

 

°f

 

Entering wb

 

 

°f

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inside db

 

 

°f

 

 

°f

 

Assume no higher than 63 °f unless there is ventilation air or significant duct leakage or heat gain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Design TD

 

 

°f

 

 

°f

 

If design conditions used are not those listed in Table 1 / 1A Manual 3, please justify.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Infiltration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Method

 

 

 

 

 

 

 

 

Construction quality

 

 

 

 

 

 

 

 

# of fireplaces

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual J heat loss

 

 

 

 

btuh

 

Heating fan

 

 

 

 

CFM

 

Htg design TD

 

°f

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp rise range

 

 

 

 

to

 

 

°f

 

Latent gain

 

 

 

 

btuh

 

Total gain

 

 

btuh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual J sensible gain

 

 

 

btuh

 

Cooling fan

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Use SHR to determine cooling CFM / ton

 

 

 

 

 

 

 

 

 

 

 

Calculated SHR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Furnace manufacturer

 

 

 

 

 

 

 

Model #

 

 

 

 

 

 

 

AFUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sea level: input

 

 

 

 

 

 

btuh

 

Output

 

 

 

 

 

 

 

Altitude adjusted output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multistage

 

If yes, provide

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Altitude adjusted lowest output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If “adjusted output” is greater than 1.4 times the “total heating load”, please justify

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling Equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC manufacturer

 

 

 

 

 

 

 

 

 

Model #

 

 

 

 

 

 

 

SEER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total capacity

 

 

 

 

 

 

btuh

 

Sensible capacity

 

 

 

btuh

 

Latent capacity

 

btuh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator coil manufacturer

 

 

 

 

 

 

 

 

 

Model #

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multistage

 

TXV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Metering

 

Actual SEER rating w/ selection coil, furnace, & metering

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Attach manufacturer’s data showing actual cooling capacity and actual SEER using these components

If “cooling capacity” is greater than 1.15 times the “total heating load”, please justify

Manual J / S Summary

Instructions

The load information asked for on the summary must be taken from the actual load calculation completed on the project.

Project

Identify project name, lot number- information that matches the plan submitted.

Location

The city or town must be reasonably close to actual location. Software used may not have the specific location in the database.

Outside Dry Bulb, Inside Dry Bulb

Temperature data should be from Table 1 or Table 1A of ACCA Manual J. It is understood that there may be situations where a slight adjustment to this values is necessary. For example; there may be areas in the Salt Lake Valley where the low temperature is historically lower than the airport temperature. If values are adjusted- please justify the adjustment. Provide both heating (htg) and cooling (clg) design temperatures. If inside

or outside design conditions listed are not the same values listed in Manual J, explain why the different values were used.

Entering WB

The entering wet-bulb represents the default value wet-bulb temperature across the evaporator coil. This will typically be

63 °f (75 °f dry bulb) relative humidity). A higher wb temperature will result from duct leakage, un-insulated duct or ventilation air- any condition that raises the return

air temperature. Use this wb temperature when selecting cooling condenser from manufacturer’s comprehensive data.

Design TD

TD: the temperature difference between inside and outside design temperatures.

Infiltration

Infiltration calculations are based on the Construction Quality. Version 7 of Manual ] uses Best, Average or Poor to evaluate Infiltration. Version 8AE uses Tight, Semi-Tight, Average, Semi-Loose and Loose to evaluate. Version 8 goes into very specific detail for a more accurate number. Note method used on summary. Open firebox fireplaces that draw air from inside the home must be included, even if there is a 4” ‘combustion air’ flex bring air into the fireplace. Sealed, direct vent type fireplaces should

not be counted. Methods include: Simplified

/Default Method- taken from Table 5A; Component Leakage Area Method- calculating infiltration based on individual leakage points taken from Table 5C of Manual J8; or Blower Door Method, where the actual leakage is based on a blower door test on the home.

Manual J Heat Loss

This is the whole house winter heat loss taken directly from the completed attached Load Calculation. Load must account for all factors such as loss building components as well as loss through infiltration, ventilation, and duct losses.

Heating Fan

Heating airflow typically may be lower than cooling cfm. Adjusted to insure the temperature rise across the heat exchanger falls within the range specified by the manufacturer. Software will often do this calculation and provide a correct heating cfm. See Manual S Section 2-6 - Rise (°f) = Output Capacity ÷ (1.1 x heating cfm)

Manufacturer’s Temperature Rise Range

Range taken from manufacturer’s performance data. Various manufacturers may certify ranges from 20 - 70 °f.

Manual J — Sensible Gain

The whole house summer heat gain taken directly from the completed attached Load Calculation. Load must account for all factors including gain through building components, solar gain, infiltration, ventilation and ducts. Also includes the sensible internal gains from appliances and people.

Manual 3 — Latent Gain

The gains due to moisture in the air. Large latent load are typically from moisture migration into the home from outside in humid climates. People, cooking, plants, bathing and laundry washing can all add to the latent load in a home.

Total Gain

The combined total of the sensible and latent gain. May be referred to as Total Cooling Load.

SHR- Sensible Heat Ratio

Use to determine Cooling cfm per ton. The ratio of sensible heat gain to total heat gain. SHR = Sensible Heat Gain ÷ Total Heat Gain. Recommended air flows: If SHR is below 0.80 select 350 cfm / ton; if SHR is between 0.80 & 0.85 select 400 cfm; if SHR is greater than 0.85, select 450 cfm

/ton. Note: This cfm is not the final cfm; additional adjustment may be required for Altitude. See next item- Cooling Fan.

Cooling Fan

Software used to perform the calculation will typically provide a minimum cfm based on the minimum required size of the equipment. This number may be adjusted to meet specific requirements of the home. Heating and Cooling CFM may or may not be the same. The cooling CFM should be around 450 CFM per ton of cooling in Utah’s dry climates. For higher altitudes, CFM must be adjust up as detailed in ACCA / ANSI Manual S. Mountain location should expect Cooling CFM at 500 CFM per ton and higher.

HEATING

Equipment

List specific equipment to be used. This information is not required on the Load Calculation documents, however it must be provided here to verify equipment sizing against calculated loads.

AFUE

The AFUE (Annual Fuel Utilization Efficiency) listed here will be compared to that listed on plans and on energy compliance documents (RES check or other). It must also match the equipment actually installed in the home.

Sea Level Input

The listed input on the furnace label and in manufacturers’ documentation. Input represents the total amount

of heat in the gas at sea level.

Output

The amount a heat available for discharge into the conditioned space. The input less any vent or stack losses, or heat that is carried out with the products of combustion. May be take from manufacturer’s performance data or calculated using input and furnace efficiency.

Altitude Adjusted Output

This number is the actual output that will be attained after the furnace has been adjusted for efficiency and de-rated for altitude (typically 4% for every 1000’ above sea-level, however 2% /1000’ for many 90+ efficient furnaces). Some manufacturers may have different requirements- adjustments should be made per their requirements. Calculations should be attached. Example: 80,000 input 91% efficient furnace in Salt Lake, with manufacturers’ installation instructions specifying 4% / 1000’. 80,000 x .91 x .83 = 60,424 btuh.

Multi-Stage Furnace

Multi-stage and modulating equipment is now available. When comparing to heating load calculated, use the maximum adjusted output to verify the furnace is large enough and the lowest output to insure it is not too large.

Size Justification

Example: If the Total Heating Load = 29954 btuh. A furnace with an adjusted output larger than 45,000 btuh (29954 x 1.5 = 44931) would require an explanation justifying the size.

COOLING

Equipment

List specific equipment to be used. Provide manufacturers comprehensive data for furnace, furnace blower and condenser, with capacities at design conditions highlighted.

Condenser SEER

This SEER (Seasonal Energy Efficiency Ratio) is the listed SEER for this model series, not the exact SEER with components used this system.

Total Capacity

Manufacturers base data is based on ARI Standard 210 / 240 ratings; 95 °f outdoor air temperature, 80 °f db / 67 °f wb entering evaporator. As the Design Conditions

are different than this standard, refer to manufacturers expanded ratings for capacities at actual design conditions. Total capacity is the latent and sensible capacity at design conditions

Sensible Capacity

The sensible only capacity from the manufacturer’s expanded data at design conditions.

Manual D Calculations & Summary

Project

Friction Rate Worksheet & Steps

1Manufacturer’s Blower Data

External static pressure (ESP)

IWC

CFM

 

 

 

Latent Capacity

The latent only capacity from the manufacturer’s expanded data at design conditions. NOTE: One half of the excess latent capacity may be added to the sensible capacity.

Evaporator Coil Make and Model #

List the exact model number for the evaporator coil used this system. If coil is from a different manufacturer than the condenser is used, provide data from both manufacturers verifying actual performance.

Expansion / Metering

Provide the specific metering used- orifice or TXV (thermostat expansion valve). If the manufacturer has several options, list the option used.

Actual SEER Rating

Attach manufacturers’ documentation or ARI report showing actual cooling capacity, and actual SEER using the components used this system. Indoor air handler / furnace blower must be included in this documentation. Do not use ARI (ARHI) data for actual sizing.

Size Justification

If cooling capacity is 15% greater than the calculated Cooling load explain. High latent (moisture) loads can be listed here. Special requirements particular to the customer may also be noted here.

2Device Pressure Losses

Evaporator

Supply register

.03

Other device

 

 

 

 

 

 

 

 

 

 

 

Air filter

Return grill

.03

Total device losses (DPL)

IWC

 

 

 

 

 

3Available Static Pressure (ASP)

ASP = ( ESP - DPL ) IWC

4Total Effective Length (TEL)

Supply side TEL

ft

 

Return side TEL

ft

 

 

 

 

 

Total effective length (TEL) = supply side TEL + return side TEL ft

5Friction Rate Design Value (FR)

FR = ( ( 100 x ASP ) / TEL ) IWX / 100’

Mechanical Sizing

Name of contractor / designer

Phone Fax

Address

Permit # Lot #

This friction rate (FR) calculated in Step 5 is the rate to be used with a duct calculator or a friction chart for the duct design on this project.

Attach at a minimum, a one line diagram showing the duct system with fittings, sizes, equivalent lengths through fitting and duct lengths.

Vent height (base of duct to roof exit) ft

Boiler or furnace input rating

btu

 

 

 

 

De-rated input rating (use .83)

btu

 

 

 

 

Connector rise

ft

 

 

 

 

Connector run

ft

 

 

 

 

Connector size

in

 

 

 

 

Orifice size

in

 

 

 

 

Water heater input rating

btu

 

 

 

 

De-rated input rating (.83 minimum)

btu

 

 

 

 

Connector rise

ft

 

 

 

 

Connector run

ft

 

 

 

 

Connector size

in

 

 

 

 

Orifice size

in

 

 

 

 

Total heat input of all appliances

btu

 

 

 

 

Vent size for the system

in

 

 

 

 

Combustion air size

in²

 

 

Signature

 

Boiler or furnace #2 input rating btu

De-rated input rating (use .83) btu

Connector rise ft

Connector run ft

Connector size in

Orifice size in

Water heater #2 input rating btu

De-rated input rating (.83 minimum) btu

Connector rise ft

Connector run ft

Connector size in

Orifice size in

Attach a complete gas pipe layout & sizing detail to the plan or permit application.

If a manifold is used to connect the appliances on the horizontal, it shall be the same size as the vent.

To the best of my knowledge, I certify that the information contained within this document is true, correct, and meets the requirements of the 2009 International Mechanical Code and International Fuel Gas Code.

Date

Mechanical Sizing Worksheet

 

b

Example: SLC has a 17% de-ration

How-To

 

 

factor. On a 100,000 Btu furnace you

Materials needed to fill out this form are the

 

 

multiply 100,000 x .83 = 83,000 Btu’s

 

c

On the vent sizing this becomes

International fuel gas Code and the Questar

 

Recommended Good Practices Book.

 

 

the fan min. The fan max is the

VENT SIZING

 

 

listed input rate example fan

 

 

min = 83 and fan max = 100

1

Vent height is measured from the

 

d

The Btu to ft³ conversion number for

 

draft diverter or appliance vent

 

 

SLC is 890 and the specific gravity of

 

outlet to the top of the vent cap.

 

 

the gas is .60. Divide the new input

2

Connector rise is the height of the vent

 

 

rating by 890, 83,000 = 93.258 ft³. 890

 

 

 

 

connector from the appliance outlet

 

e

Take the ft³ of input and divide it by the

 

to the center of the tee in the vent at

 

 

number of burners on the appliance,

 

the point of connection to the vent.

 

 

this will give you the ft³ / burner. Then

3

Connector run is the horizontal distance

 

 

use the orifice tables in the Questar

 

 

handbook to determine the orifice size.

 

from the appliance vent outlet to the vent.

 

 

 

 

 

Example if you have 4 burners: 93.258

 

 

 

 

4

Go to the International Fuel Gas

 

 

ft³ / 4 burners = 23.315 ft³ / 1 burner.

 

Code Chapter 5. Sizing is done to

 

 

Match as close as possible to the

 

the appropriate gamma table .

 

 

Orifice table in the handbook. In this

5

The gamma tables are in Btu and not ft³

 

 

sample the orifice size would be (49)

2

Use the International Fuel Gas Code and the

DE-RATING

 

International Mechanical Code to complete

 

 

 

1

See Questar handbook for a step-by-step

 

the vent sizing and the combustion air

 

sizing. See Chapter 5 IFC for the rules and

 

formula and the required conversion

 

 

 

the tables to fill out this portion of the form.

 

numbers. To complete this form:

 

 

 

ICBO also has available a commentary on

 

 

 

 

a Input is de-rated at 4% per

 

the mechanical code that contains a step-

 

1000’ in elevation.

 

by-step examples of how to size the vents.

3The International Mechanical Code commentary also contains examples to size the gas pipe. You must show the pipe lengths, the Btus and the volume of each appliance and show the size of each length of pipe. All tables necessary to size gas pipe are also contained in the International Fuel Gas Code, and in the Questar handbook.

4For Salt Lake City use:

a890 Btu per ft³

bA multiplier of .83

cSpecific gravity of .60

dCombustion air is computed at 1 in² per 3,000 Btu of input of all fuel burning appliances in the room. One duct upper 12” of the room.

EQuestar gas has a training program available to all persons and contractors.

How to Edit Printable Manual J Form Online for Free

Creating forms using this PDF editor is simpler in comparison with anything else. To edit blank manual j forms the document, there isn't anything you should do - simply proceed with the steps below:

Step 1: Search for the button "Get Form Here" and hit it.

Step 2: Now you are on the file editing page. You can modify and add text to the document, highlight words and phrases, cross or check specific words, include images, put a signature on it, erase unnecessary fields, or eliminate them completely.

The following areas will make up your PDF file:

manual j load calculation sheet empty spaces to complete

Fill out the Design TD, If design conditions used are not, Infiltration, Method, Summary, Construction quality, of fireplaces, Manual J heat loss, btuh, Heating fan, CFM, Htg design TD, Temp rise range, Latent gain, and btuh section with the particulars asked by the system.

manual j load calculation sheet Design TD, If design conditions used are not, Infiltration, Method, Summary, Construction quality, of fireplaces, Manual J heat loss, btuh, Heating fan, CFM, Htg design TD, Temp rise range, Latent gain, and btuh fields to fill out

Note all details you need inside the box Cooling Equipment, AC manufacturer, Total capacity, Model, SEER, btuh, Sensible capacity, btuh, Latent capacity, btuh, Evaporator coil manufacturer, Model, Metering, Multistage, and TXV.

manual j load calculation sheet Cooling Equipment, AC manufacturer, Total capacity, Model, SEER, btuh, Sensible capacity, btuh, Latent capacity, btuh, Evaporator coil manufacturer, Model, Metering, Multistage, and TXV blanks to fill out

The Manual D Calculations Summary, Project, Friction Rate Worksheet Steps, Manufacturers Blower Data, External static pressure ESP, IWC, CFM, Device Pressure Losses, Evaporator, Air filter, Available Static Pressure ASP, ASP ESP DPL, IWC, Supply register, and Other device section is the place to indicate the rights and responsibilities of both parties.

Completing manual j load calculation sheet step 4

Look at the areas Attach at a minimum a one line, Friction Rate Design Value FR, FR x ASP TEL, IWX, Mechanical Sizing, Name of contractor designer, Phone, Address, Permit, Fax, Lot, and Vent height base of duct to roof and then fill them in.

Finishing manual j load calculation sheet stage 5

Step 3: Once you select the Done button, your finalized document can be simply exported to each of your gadgets or to electronic mail chosen by you.

Step 4: To protect yourself from any sort of concerns later on, be sure to get as a minimum several copies of your file.

Watch Printable Manual J Form Video Instruction

Please rate Printable Manual J Form

1 Votes
If you believe this page is infringing on your copyright, please familiarize yourself with and follow our DMCA notice and takedown process - click here to proceed .